Rockwell Automation 193-EC4 EC4 Current Monitoring Relay User Manual User Manual

Page 65

Advertising
background image

66

Rockwell Automation Publication 193-UM011A-EN-P - September 2010

Chapter 5 Programmable Parameters

PM - # Starts

This parameter allows the installer to set a
number of starts after which preventative
maintenance should be performed.

Parameter Number

101

Access Rule

Get/Set

Data Type

UINT

Object Mapping

29hex-1-106

Group

Advanced Setup

Units

Minimum Value

0

Maximum Value

65535

Default Value

0

GF Warn Delay

This parameter allows the installer to
program a time duration for which a ground
fault condition must exist at the programmed
level prior to the device providing a warning.

Parameter Number

105

Access Rule

Get/Set

Data Type

USINT

Object Mapping

2Chex-1-180

Group

Advanced Setup

Units

Seconds

Minimum Value

0

Maximum Value

250

Default Value

0

PM - Oper. Hours

This parameter allows the installer to set the
hours of operation after which preventative
maintenance should be performed.

Parameter Number

102

Access Rule

Get/Set

Data Type

UINT

Object Mapping

29hex-1-107

Group

Advanced Setup

Units

Hours

Minimum Value

0

Maximum Value

65535

Default Value

0

UC Inhibit Time

This parameter sets the time in which the
under current protection is inhibited during a
starting sequence.

Parameter Number

107

Access Rule

Get/Set

Data Type

USINT

Object Mapping

2C

hex

-1-158

Group

Advanced Setup

Units

Seconds

Minimum Value

0

Maximum Value

250

Default Value

1