Rockwell Automation 193-EC4 EC4 Current Monitoring Relay User Manual User Manual

Page 134

Advertising
background image

Rockwell Automation Publication 193-UM011A-EN-P - September 2010

135

DeviceNet Information Appendix B

The following common services will be implemented for the Parameter Object:

Table 47 - Parameter Object Instance Attributes

Attribute
ID

Access Rule

Name

Data Type

Value

1

Get/Set
(Only Get is
supported for
monitoring
parameters)

Parameter Value

See Data Type
& Data Size
Attributes

2

Get

Link Path Size

USINT

08

3

Get

Link Path

Segment Type/Port
Segment Address

BYTE
Path Data
Dependent

Path to specific device
object attribute if
applicable

4

Get

Descriptor

WORD

Parameter
Dependent:
0000000000ab0cd0

a - Monitoring
Parameter
b - Read Only
Parameter
c - Scaled Parameter
d - Enumerated String

5

Get

Data Type

USINT

Parameter Dependent

6

Get

Data Size

USINT

Parameter Dependent

7

Get

Parameter Name

SHORT_STRI
NG

Parameter Dependent

8

Get

Units String

SHORT_STRI
NG

Parameter Dependent

10

Get

Minimum Value

Data Type

Parameter Dependent

11

Get

Maximum Value

Data Type

Parameter Dependent

12

Get

Default Value

Data Type

Parameter Dependent

13

Get

Scaling Multiplier

UINT

01

14

Get

Scaling Divisor

UINT

01

15

Get

Scaling Base

UINT

01

16

Get

Scaling Offset

INT

00

17

Get

Multiplier Link

UINT

0

18

Get

Divisor Link

UINT

0

19

Get

Base Link

UINT

0

20

Get

Offset Link

UINT

0

21

Get

Decimal Precision

USINT

Parameter Dependent

Advertising