Chapter 5 Programmable Parameters

NONVOL BAUD RATE

This parameter allows the installer to
manually set the desired baud rate.

Parameter 55, AutoBaud Enable, must be
disabled when using this parameter.

Parameter Number

56

Access Rule

Get/Set

Data Type

USINT

Object Mapping

0xB4-1-6

Group

DeviceNet Setup

Units

Minimum Value

0 = 125k
1 = 250k

Maximum Value

2 = 500k

Default Value

0

COS MASK

This parameter allows the installer to define
the change-of-state conditions that will
result in a change-of-state message being
produced.

1 = Enabled
0 = Disabled

Parameter Number

58

Access Rule

Get/Set

Data Type

WORD

Object Mapping

0xB4-1-13

Group

DeviceNet Setup

Units

Minimum Value

0000000000000000

Maximum Value

0000001111111111

Default Value

0000000000000000

Bit

Function:

15 14 13 12 11 10 9

8

7

6

5

4

3

2

1

0

X

Trip

X

Warning

X

Output A

X

Output B (E3 Plus)

X

Input #1

X

Input #2

X

Input #3 (E3 Plus)

X

Input #4 (E3 Plus)

X

Motor Current

X

Ground Fault Current (E3 Plus)

OUTPUT ASSEMBLY

This parameter is used to select the desired
output assembly. See Appendix B for a listing
of available assemblies

Parameter Number

59

Access Rule

Get/Set

Data Type

USINT

Object Mapping

0xB4-1-16

Group

DeviceNet Setup

Units

Minimum Value

0

Maximum Value

105

Default Value

103 (E3)
105 (E3 Plus)