Rockwell Automation 193-EC4 EC4 Current Monitoring Relay User Manual User Manual

Page 54

Advertising
background image

Rockwell Automation Publication 193-UM011A-EN-P - September 2010

55

DeviceNet Node Commissioning Chapter 4

Figure 30 - I/O Assembly Settings

Selection of Input and Output Assemblies (also referred to as Produced and
Consumed Assemblies) define the format of I/O message data that is exchanged
between the EC4 Current Monitoring Relay and other devices on the network.
The consumed information is generally used to command the state of the slave
device’s outputs, and produced information typically contains the state of the
inputs and the current fault status of the slave device.

The default Consumed and Produced Assemblies are shown in Table 14 and
Table 15; for additional formats refer to Appendix B.

Table 14 - Instance 100 - Default Produced IO Assembly

Instance 100 Parameter Based Input Assembly

Byte

Word

Value

0

0

Value of parameter pointed to by parameter #61 (low byte)

1

Value of parameter pointed to by parameter #61 (high byte)

2

1

Value of parameter pointed to by parameter #62 (low byte)

3

Value of parameter pointed to by parameter #62 (high byte)

4

2

Value of parameter pointed to by parameter #63 (low byte)

5

Value of parameter pointed to by parameter #63 (high byte)

6

3

Value of parameter pointed to by parameter #64 (low byte)

7

Value of parameter pointed to by parameter #64 (high byte)

Advertising