Parameter object – class code 0x0f – Rockwell Automation 193-EC4 EC4 Current Monitoring Relay User Manual User Manual

Page 133

Advertising
background image

134

Rockwell Automation Publication 193-UM011A-EN-P - September 2010

Appendix B DeviceNet Information

Multiple instances of the Discrete Output Point Object are supported, one
instance for each general purpose discrete output on the EC4 Current
Monitoring Relay. All instances will contain the following attributes:

The following common services are implemented for the Discrete Output Point
Object:

Parameter Object – Class
Code 0x0F

The following class attributes are supported for the Parameter Object:

Multiple instances of the Parameter Object are supported. All instances will
contain the following attributes:

Table 44 - Discrete Output Point Object Instance Attributes

Attribute ID

Access
Rule

Name

Data Type

Value

3

Get/Set

Value

BOOL

Output point value.
0 = OFF; 1 = ON

5

Get/Set

Fault Action

BOOL

0 = Go to fault value
1 = Hold last state

6

Get/Set

Fault Value

BOOL

0 = OFF
1 = ON

7

Get/Set

Idle Action

BOOL

0 = Go to Idle Action
1 = Hold Last State

8

Get/Set

Idle Value

BOOL

0 = OFF
1 = ON

113

Get/Set

Protection Fault Action

BOOL

0 = Go to Pr Fault Value
1 = Ignore

114

Get/Set

Protection Fault Value

BOOL

0 = OFF
1 = ON

Table 45 - Discrete Output Point Object Common Services

Service
Code

Implemented for:

Service
Name

Class

Instance

0x0E

Yes

Yes

Get_Attribute_Single

0x10

No

Yes

Set_Attribute_Single

Table 46 - Parameter Object Class Attributes

Attribute
ID

Access
Rule

Name

Data Type

Value

1

Get

Revision

UINT

1

2

Get

Max Instances

UINT

Product Code
Dependent

8

Get

Parameter Class
Descriptor

WORD

0x03

10

Get

Native Language

USINT

1 = English