Rockwell Automation 193-EC4 EC4 Current Monitoring Relay User Manual User Manual

Page 68

Advertising
background image

Rockwell Automation Publication 193-UM011A-EN-P - September 2010

69

Programmable Parameters Chapter 5

For Catalog Number 193-EC4ZZ

For Catalog Number 193-EC4ZZ

L3 UC Warn Level

This parameter sets the under current
warning level for line 3.

Parameter Number

116

Access Rule

Get/Set

Data Type

UINT

Object Mapping

2C

hex

-1-167

2C

hex

-1-120

Group

Advanced Setup

Units

0.01 Amps
1 Amps

Minimum Value

0.20

Maximum Value

5000

Default Value

OC Inhibit Time

This parameter sets the time in which the
over current protection is inhibited during a
starting sequence.

Parameter Number

117

Access Rule

Get/Set

Data Type

USINT

Object Mapping

2C

hex

-1-168

Group

Advanced Setup

Units

Seconds

Minimum Value

0

Maximum Value

250

Default Value

1

L1 OC Trip Level

This parameter sets the over current trip
level for line 1.

Parameter Number

118

Access Rule

Get/Set

Data Type

UINT

Object Mapping

2C

hex

-1-169

2C

hex

-1-187

Group

Advanced Setup

Units

0.01 Amps
1 Amps

Minimum Value

0.20

Maximum Value

5000

Default Value

L1 OC Trip Delay

This parameter allows the installer to
program a time duration for which an over
current condition must exist at the
programmed level prior to the device
tripping.

Parameter Number

119

Access Rule

Get/Set

Data Type

USINT

Object Mapping

2C

hex

-1-170

Group

Advanced Setup

Units

0.1 Seconds

Minimum Value

0.1

Maximum Value

25.0

Default Value

1.0