Rockwell Automation Publication 193-UM011A-EN-P - September 2010

79

Programmable Parameters Chapter 5

OUTB PR FLTVALUE

This parameter determines the state that
Output B assumes when a trip occurs and
Parameter 71 is set to “0”.

Parameter Number

72

Access Rule

Get/Set

Data Type

BOOL

Object Mapping

0x09-2-114

Group

DeviceNet I/O

Units

Minimum Value

0 = Open

Maximum Value

1 = Closed

Default Value

0

OUTB DN FLTSTATE

This parameter, in conjunction with
Parameter 74, defines how Output B will
respond when a DeviceNet network fault
occurs. When set to “1”, Output B will hold
the state prior to trip occurrence. When set
to “0”, Output B will open or close as
determined by the setting in Parameter 74.

Output B can be configured to go to a desired
state in the event of a DeviceNet network
fault independent from enabling CommFault
in Parameter 24, Trip Enable.

Parameter Number

73

Access Rule

Get/Set

Data Type

BOOL

Object Mapping

0x09-2-5

Group

DeviceNet I/O

Units

Minimum Value

0 = Go to FltValue (#74)

Maximum Value

1 = Hold Last State

Default Value

0

OUTB DN FLTVALUE

This parameter determines the state that
Output B assumes when a comm fault occurs
and Parameter 73 is set to “0”.

Parameter Number

74

Access Rule

Get/Set

Data Type

BOOL

Object Mapping

0x09-2-6

Group

DeviceNet I/O

Units

Minimum Value

0 = Open

Maximum Value

1 = Closed

Default Value

0

OUTB DN IDLSTATE
This parameter, in conjunction with
Parameter 76, defines how Output B will
respond when the DeviceNet network is idle.
When set to “1”, Output B will hold the state
prior to trip occurrence. When set to “0”,
Output B will open or close as determined by
the setting in Parameter 76.

The Dn Flt parameters supersede the Dn Idl
parameters.

Parameter Number

75

Access Rule

Get/Set

Data Type

BOOL

Object Mapping

0x09-2-7

Group

DeviceNet I/O

Units

Minimum Value

0 = Go to IdlValue (#76)

Maximum Value

1 = Hold Last State

Default Value

0

OUTB DN IDLVALUE

This parameter determines the state that
Output B assumes when the network is idle
and Parameter 75 is set to “0”.

Parameter Number

76

Access Rule

Get/Set

Data Type

BOOL

Object Mapping

0x09-2-8

Group

DeviceNet I/O

Units

Minimum Value

0 = Open

Maximum Value

1 = Closed

Default Value

0