Assembly object – class code 0x04, Output assemblies – Rockwell Automation 193-EC4 EC4 Current Monitoring Relay User Manual User Manual

Page 125

Advertising
background image

126

Rockwell Automation Publication 193-UM011A-EN-P - September 2010

Appendix B DeviceNet Information

➊ Allocation byte

Bit 0

Explicit Messaging

Bit 1

Polled I/O

Bit 4

Change of State I/O

Bit 5

Cyclic I/O

Bit 6

Acknowledge Suppress I/O

The following services are implemented for the DeviceNet Object:

Assembly Object – Class
Code 0x04

Output Assemblies

The following Assembly Instances are implemented. Note that most of these
assemblies are part of the “motor control hierarchy” of the DeviceNet
specification. Other vendor specific assemblies have been added to allow the
monitoring of the auxiliary inputs, etc.

The following assemblies are similar to those found in the Motor Starter Profile.
The only difference is that OutA and OutB map to Discrete Output Points
instead of the Control Supervisor. The instance numbers are 100 plus the
number assigned in corresponding assemblies in the Motor Starter Profile.

Table 17 - DeviceNet Object Instance Attributes

Attribute
ID

Access
Rule

Name

Data Type

Value

1

Get/Set

MAC ID

USINT

0...63

2

Get/Set

Baud Rate

USINT

0 = 125 kbaud
1 = 250 kbaud
2 = 500 kbaud

5

Get

Allocation Information

Allocation’s Choice Byte
Master’s MAC ID

Structure
of:

BYTE
USINT

Allocation byte ➊
0...63 = address
255 = unallocated

Table 18 - DeviceNet Object Common Services

Service
Code

Implemented for:

Service Name

Class

Instance

0x0E

Yes

Yes

Get_Attribute_Single

0x10

No

Yes

Set_Attribute_Single

0x4B

No

Yes

Allocate_Master/Slave_Connection_Set

0x4C

No

Yes

Release_Master/Slave_Connection_Set

Table 19 - Assembly Object Instance 2 Data Format (“TRIP RESET CMD”)

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit3

Bit 2

Bit 1

Bit 0

0

Fault
Reset