Chapter 2 Installation and Wiring

Control and DeviceNet Terminals

For reliable input signal processing, input wiring should be routed in raceways
separate from power cabling.

Terminal Designations

Control Terminals

The following table defines the EC4 Current Monitoring Relay control terminal
designations.

Table 3 - Control and DeviceNet Terminal Wire Size and Torque Specification

Cat. No.

All Types

Stranded/Solid
AWG

Single Conductor
Multiple Conductor
Torque

24...12 AWG
24...16 AWG
5 lb-in

Flexible-Stranded with Ferrule
Metric

Single Conductor
Multiple Conductor
Torque

0.25...2.5 mm

2

0.5...0.75 mm

2

0.55 Nm

Coarse-Stranded/Solid
Metric

Single Conductor
Multiple Conductor
Torque

0.2...4.0 mm

2

0.2...1.5 mm

2

0.55 Nm

Table 4 - Maximum Wire Lengths (Input)

Min. Cross
Section

mm

2

0.5

0.75

1.5

2.5

4.0

AWG

20

18

16

14

12

Max.
Length

m

160

250

400

600

1000

ft

525

825

1300

1950

3200

Table 5 - Ground Fault Sensor Terminals (S1 and S2)

Wire type

Shielded, twisted pair

Cross section

0.2…4.0 mm

2

(#24…12 AWG)

Torque

0.55 N

m (5 lb-in.)

Table 6 - Control Terminal Designation

Terminal
Designation

Reference

Description

1

IN 1

General-purpose sinking input number 1

2

IN 2

General-purpose sinking input number 2

3

IN 3

General-purpose sinking input number 3

4

IN 4

General-purpose sinking input number 4

5

V+

+24V DC supply for inputs

6

V+

End

Earth Ground

13/14

OUT A

Output A

23/24

OUT B

Output B