Publication 1404-UM001D-EN-E - October 2004

4-44 Communications

Figure 4.11 I/O Connection Setup

Select ‘Data – INT’ as the Communications Format. Enter the IP
address of the Powermonitor 3000. Set the Connection Parameters as
shown for the default configuration. If you change the configuration
of the input assembly instance, enter its new size in Instance 1 here.
Select 3 as the Configuration instance and leave its Size set to 0 bytes
(the Series B Powermonitor 3000 does not support a Class 1
configuration connection). Click the Next> button.

Figure 4.12 Requested Packet Interval Setup

Set the Requested Packet Interval to 100 mS or greater. The
Powermonitor 3000 will not respond reliably to an RPI of less than
100 mS.

The Powermonitor 3000 data will be found in controller tags as shown
in Figure 4.13.