Publication 1404-UM001D-EN-E - October 2004

A-54 Powermonitor 3000 Data Tables

Table A.43 Transient Analysis Configuration/Read-Back Select

CSP File No.

F43

Remote I/O BT

44

CIP Assy. Inst.

52 (Write), 53 (Read)

No. of Elements

10

User Configurable No

Data Type

Floating Point

Data Access

Read / Write

PM3000 Type

M8 only

Applies to:

Table 43: Transient analysis metering results

Element
No.

Modbus
Address

Element name

Range

Default
Value

Comment

0

-

Password

0 to 9999

0

Required for configuration, -1 for readback select,
returns -1.

1

-

DeviceNet unique write
identifier

-32768 to 32767

0

Refer to DeviceNet Unique Write Identifier on
page 4-36.

2

-

Capture #

0 to 6

1

Refer to Transient Analysis Configuration on
page 8-19.

3

-

Cycle #

1 to 12

1

4

-

Read-back mode

0 to 1

0

5

-

Detection mode

0 to 3

1

6

-

Reserved

0

0

7

-

Auto-threshold set command

0 to 1

0

8

-

Auto-threshold set duration

1 to 3600

10

9

-

Auto-threshold set margin

1.0 to 100.0

20.0

10

-

Voltage trigger threshold

0.1 to 100.0

10.0

11

-

Current trigger threshold

0.1 to 100.0

10.0

12

-

Auto-threshold duration time
left

0

0