Publication 1404-UM001D-EN-E - October 2004

4-38 Communications

Ethernet PCCC/CSP protocol

PCCC messaging is supported in the Series A Powermonitor 3000 and
in Series B units with communications firmware 1.22 and Master
Module firmware 2.5x or later.

You may set up messaging from legacy controllers such as PLC-5 and
SLC 500, to a Powermonitor 3000 with optional Ethernet

Table 4.11 Ethernet Message Types

Message type

Series A

Series B

CIP PLC-5 Typed Write

CIP PLC-5 Typed Read

CIP Generic Assembly Object (class 04), Get & Set Attribute Single
for Attribute 3 (data)

CIP Generic Assembly Object (class 04), Get Attribute Single for
Attribute 3 (size)

CIP SLC 500 Typed Write

(1)

(1) Available in communications FRN 1.21 or later.

CIP SLC 500 Typed Read

(1)

CIP Data Table Read (using CSP/PCCC addressing e.g. F15:0)

(1)

CIP Data Table Write

(1)

CSP / PCCC PLC-5 Typed Write

(2)

(2) Available in communications FRN 1.22 or later. Uses CIP Encapsulation on PCCC commands.

CSP / PCCC PLC-5 Typed Read

(2)

CSP / PCCC Protected Typed Logical Read, 2 address fields

(2)

CSP / PCCC Protected Typed Logical Read, 3 address fields

CSP / PCCC Protected Typed Logical Write, 2 address fields

(2)

CSP / PCCC Protected Typed Logical Write, 3 address fields

CSP / PCCC Word Range Read

(2)

CSP / PCCC Word Range Write

(2)

CSP / PCCC Diagnostic Loopback

IMPORTANT

For future compatibility, it is recommended that you
use EtherNet/IP messaging with Series A
Powermonitor 3000 units.