A-14 Powermonitor 3000 Data Tables

Remote I/O

Element
No.

Modbus
Address

Element name

Range

Default
Value

Comment

0

40401

Password

0 to 9999

0

Valid password required to change configuration data. Returns -1

1

40402

Logical rack address

1 to 63

1

The scanner uses rack address 0

2

40403

Module group

0,2,4,6

0

0 = Group 0 (acts like the first 2 rack slots)
2 = Group 2
4 = Group 4
6 = Group 6

3

40404

Last rack

0 to 1

0

0 = No
1 = Yes

4

40405

Baud rate

0 to 2

0

0 = 57.6k baud
1 = 115.2k baud
2 = 230.4k baud

5

40406

Reserved

0

0

Reserved. Must be 0 on a write, returns 0

6

40407

7

40408

8

40409

9

40410

10

40411

11

40412

12

40413

13

40414

14

40415

15

40416

16

40417

17

40418

18

40419

19

40420