Optional remote i/o communications – Rockwell Automation 1404-M4_M5_M6_M8 Powermonitor 3000 User Manual, PRIOR to Firmware rev. 3.0 User Manual

Page 65

Advertising
background image

Publication 1404-UM001D-EN-E - October 2004

Communications 4-5

Optional Remote I/O Communications

Powermonitor 3000 units with a catalog number ending in “-RIO” are
equipped with an optional Remote I/O port in addition to the native
port. This dual-port option allows the use of both ports
simultaneously. The port emulates a logical quarter-rack of I/O. You
must configure the rack address, group number, baud rate and last
rack status. Configuration parameters are:

RIO Rack Address: The logical rack address as configured in the

Remote I/O scanner module. Range 0 to 63 decimal, default 1

RIO Group Number: Logical group number corresponding to the

Remote I/O port quarter rack. Range 0, 2, 4 or 6, default 0

RIO Last Rack: If you are using a PLC-2 based system, set this

flag for the highest-numbered rack / group addressed device on
the channel. Range 0 or 1, default 0

RIO Baud Rate: Sets the communications rate. Range: 57.6, 115

or 230 Kbaud, default 57.6. All devices on the channel must be
set to the same baud rate.

Use the Display Module under the PROGRAM > OPTIONAL
COMMUNICATIONS

menu to set or modify Remote I/O

communications parameters.

TIP

For a logical rack address of 63 decimal, do not use
group number 2, 4 or 6. Powermonitor 3000 logical
rack addresses are expressed in decimal. You may
need to convert addresses to octal (range 0 to 77) for
some PLC applications.

Advertising