A-16 Powermonitor 3000 Data Tables

RS-232

Element
No.

Modbus
Address

Element name

Range

Default

Value

Comment

0

40401

Password

0 to 9999

0

Required to change configuration data. Returns -1

1

40402

Hardware port

0 to 1

0

Select active port
0 = RS-232 port
1 = Native RS-485 port

2

40403

Protocol

0

0

0 = DF1 half-duplex slave

3

40404

Delay

0 to 15

2 (10mS)

Specifies the delay before responding to an external request.,
useful with slow external devices (such as RF modems)

4

40405

Baud rate

0 to 4

3

0 = 1200 baud
1 = 2400 baud
2 = 4800 baud
3 = 9600 baud
4 = 19200 baud

5

40406

RS-232 address

1 to 254

(1)

Identifies the device on the link. 0 is typically used by the DF1
master. 255 is the broadcast address

6

40407

Data format

0 to 2

0

Parity, number of data bits, number of stop bits
0 = No parity, 8 data bits, 1 stop bit
1 = Even parity, 8 data bits, 1 stop bit
2 = Odd parity, 8 data bits, 1 stop bit

7

40408

Flow Control

(Handshaking)

0 to 1

0

Data flow control for RS-232/RS-485 port.
0 = None
1 = Hardware RTS/CTS

8

40409

RTS On Delay

0 to 9995
ms

0

9

40410

10

40411

Specifies the minimum delay between characters that indicates
the end of a message packet. 0 = 3.5 character times.

11

40412

Reserved

0

0

Reserved. Must be 0 on a write, returns 0

12

40413

13

40414

14

40415

15

40416

16

40417

17

40418

18

40419

19

40420

(1) The default address is the same as the ‘Device ID’, which is assigned at the factory and can be found printed on the white label on the side of the master module. The device ID is

incremented for each device.