Optional controlnet communications, Data messaging overview, Data messaging overview -15 – Rockwell Automation 1404-M4_M5_M6_M8 Powermonitor 3000 User Manual, PRIOR to Firmware rev. 3.0 User Manual

Page 75

Advertising
background image

Publication 1404-UM001D-EN-E - October 2004

Communications 4-15

Optional ControlNet Communications

Powermonitor 3000 units with a catalog number ending in “-CNT” are
equipped with an optional redundant ControlNet port and a native
RS-485 port in a dual-port configuration that allows simultaneous
operation of the ports. You must configure the communications
parameters before you connect the Powermonitor 3000 to a
ControlNet network. Use the Display Module under the PROGRAM >
OPTIONAL COMMUNICATIONS

menu.

The only configuration parameter is the ControlNet node number
(also called MAC ID). The range of this parameter is 1 to 99 with a
default of 99. A node number of 0 is typically used as the address of a
ControlNet scanner.

Data Messaging Overview

Through communications, the Powermonitor 3000 becomes an
effective source of power and energy data to enterprise information
and automation systems. This section of the manual provides an
overview of data messaging with the Powermonitor 3000. Following
the overview, discussions will focus on the details of messaging using
specific communications types (e.g. serial, Remote I/O, DeviceNet and
Ethernet).

Table 4.5 Optional Ethernet Communications

Parameter Description

Range

Default

User
Setting

IP Address
Bytes 1 to 4

Unit IP address in format
aaa.bbb.ccc.ddd.
0.0.0.0 enables bootp

0 to 255
decimal, each
byte

128.1.1.Unit ID

Subnet
Mask Bytes
1 to 4

Subnet mask in format
aaa.bbb.ccc.ddd

0 to 255
decimal, each
byte

255.255.255.0

Gateway IP
Address
Bytes 1 to 4

Gateway IP address in
format aaa.bbb.ccc.ddd

0 to 255
decimal, each
byte

128.1.1.1

Keep Alive
Time

Used to close out inactive
connections

0 to 3600

seconds

30 seconds

Protocol
Select
(Series A
only)

Selects the Ethernet
protocol used

0 = CSP / CIP

1 = CSP only

2 = CIP only

0 = CSP / CIP