Date and time, Table a.5 – Rockwell Automation 1404-M4_M5_M6_M8 Powermonitor 3000 User Manual, PRIOR to Firmware rev. 3.0 User Manual

Page 182

Advertising
background image

Publication 1404-UM001D-EN-E - October 2004

A-8 Powermonitor 3000 Data Tables

Table A.5 Date and Time

CSP File No.

N11

Remote I/O BT

12

CIP Assy. Inst.

6 (Write), 7 (Read)

No. of Elements

8

User Configurable No

Data Type

Integer

Data Access

Read / Write

PM3000 Type

All

Element
No.

Modbus
Address

Element name

Range

Default
Value

(2)

Comment

0

40101

Password

0 to 9999 0

Valid password required to change the date & time.
Returns -1

1

40102

Date: year

1998 to
2097

1998

1 = January, 2 = February,…12 = December
The internal clock adjusts the date for leap year.

2

40103

Date: month

1 to 12

1

3

40104

Date: day

1 to 31

(1)

1

4

40105

Time: hour

0 to 23

0

0 = 12am, 1 = 1am,…23 = 11pm
The internal clock does not adjust for daylight savings time.

5

40106

Time: minute

0 to 59

0

6

40107

Time: seconds

0 to 59

0

7

40108

Time: hundredths of seconds

0 to 99

0

(1) On a write, the maximum value for “day” depends on the values written to “month” and the “year”.

(2) The data and time default values are set if one of the following three conditions occur:

- When the device is first powered-up at the factory
- A device power-up following the depletion of the real-time clock power source
- In the event of an abnormal condition which may cause the real-time clock to contain values which are not in the valid range
The date and time are not set to the default values when “Restore Factory Defaults” is performed via the Display Module or communications port.