Metering real and apparent energy results, Table a.14 – Rockwell Automation 1404-M4_M5_M6_M8 Powermonitor 3000 User Manual, PRIOR to Firmware rev. 3.0 User Manual

Page 196

Advertising
background image

Publication 1404-UM001D-EN-E - October 2004

A-22 Powermonitor 3000 Data Tables

Table A.14 Metering Real and Apparent Energy Results

CSP File No.

N20

Remote I/O BT

29

CIP Assy. Inst.

19 (Write), 20 (Read)

No. of Elements

23

User Configurable No

Data Type

Integer

Data Access

Read / Write

PM3000 Type

All

Element
No.

Modbus
Address

Element Name

Range

Units

Default
Value

Comment

0

40501

Password

0 to 9999

-

0

Required to clear or preset energy counters.
Returns -1.

1

40502

Parameter select

0 to 7
(bitfield)

-

Refer to How to Clear or Preset Energy
Counters Using Communications on
page 4-52.

2

40503

KWh forward

### x 10

9

### x 10

6

### x 10

3

### x 10

0

### x 10

-3

-999 to 999

kWh

3

40504

4

40505

5

40506

6

40507

7

40508

KWh reverse

### x 10

9

### x 10

6

### x 10

3

### x 10

0

### x 10

-3

-999 to 999

8

40509

9

40510

10

40511

11

40512

12

40513

Kwh net

### x 10

9

### x 10

6

### x 10

3

### x 10

0

### x 10

-3

-999 to 999

13

40514

14

40515

15

40516

16

40517

17

40518

KVAh

### x 10

9

### x 10

6

### x 10

3

### x 10

0

### x 10-

3

-999 to 999

KVAh

18

40519

19

40520

20

40521

21

40522

22

40523

Metering iteration

0 to 32767

-

Increments by 1 to 32767, rolls over to 0

Advertising