Publication 1404-UM001D-EN-E - October 2004

Powermonitor 3000 Operations 3-31

Controller Command

Table A.53 is a write table consisting of one integer element. A "1"
written to bit 0 signals the end of a demand period. When this occurs,
the Master Powermonitor resets this bit to 0 and sends the end of
demand broadcast to Powermonitor units configured as "Slave
broadcast input". Bits 1 through 15 are reserved.

DST (Daylight savings time) configuration

The Powermonitor 3000 may be configured to automatically adjust its
internal clock for daylight savings time. Daylight savings time
functionality is available only in Powermonitor 3000 models with
firmware revision 2.5x or later.

To set configuration options described below using the display
module, navigate through these menus: PROG. > PASS? >
CONFIGURATION > DST.

You may also configure the daylight savings time function via
communications by writing to the Daylight Savings Time
Configuration Table A.54.

DST enable

Enables the daylight savings time function. Range 0 = disable, 1 =
enable

DST start month

Selects the calendar month when daylight savings time begins. Range
1 = January, 2 = February, … , 12 = December

DST start day

Selects the day of the week when daylight savings time begins. Range
0 = Sunday, 1 = Monday, … , 7 = Saturday

SNTP IP address 3, octet 1

0-255

0

SNTP IP address 3, octet 2

0-255

0

SNTP IP address 3, octet 3

0-255

0

SNTP IP address 3, octet 4

0-255

0

Table 3.8 Network demand/time configuration summary

Parameter name

Range

Default

User Setting