Optional rs-232 communications – Rockwell Automation 1404-M4_M5_M6_M8 Powermonitor 3000 User Manual, PRIOR to Firmware rev. 3.0 User Manual

Page 63

Advertising
background image

Publication 1404-UM001D-EN-E - October 2004

Communications 4-3

Optional RS-232 Communications

Powermonitor 3000 units with a catalog number ending in “-232” are
equipped with an optional RS-232 serial port in addition to the native
port. These units are set up at the factory to communicate using the
optional port using the Allen-Bradley DF1 half-duplex slave protocol.
The configuration parameters are:

Protocol: Allen-Bradley DF1 half-duplex slave, Modbus RTU

slave, auto-sense. Default auto-sense.

Data rate: Range 1200, 2400, 4800, 9600, 19,200 baud. Default

9600

Delay: Range 0 to 75 mS, 10 mS default
Node address: Range 1 to 247, default is unit ID listed on

nameplate

Data Format: 8 data bits, 1 stop bit, no parity or even parity.

Default no parity

Table 4.1 Native Communication Configuration Summary

Parameter Description

Range Default

User
Setting

Protocol DF1

Half-Duplex
Slave
Modbus RTU
Slave
Auto-Sense

Auto-Sense

Delay Time

between

receiving

a request and
transmitting a response

0 to 75 mS

10 mS

Baud Rate

RS-485 port
communications bit rate

1200 baud
2400 baud
4800 baud
9600 baud
19200 baud

9600 baud

RS-485 Address

Uniquely identifies the
Powermonitor device on
a multi-drop network

1 to 247

Unit ID number

Data Format

Data bits / Stop bits /
Parity

8 / 1/ none
8 / 1/ even
8 / 1/ odd

8 / 1 / none

Inter-Character
Timeout

Mimimum delay
between characters that
indicates end of Modbus
message packet

0 to 6553 ms

0 (= 3.5
character times)