Rockwell Automation 1404-M4_M5_M6_M8 Powermonitor 3000 User Manual, PRIOR to Firmware rev. 3.0 User Manual

Page 275

Advertising
background image

Publication 1404-UM001D-EN-E - October 2004

Sample Applications C-21

Data Files Used

The reset word for the sequencer is N10:0. The first word in the
rotation of the sequencer is N10:1. The value in N10:0 must be the
same as that in N10:1. The size of file N10 is equal to the size of the
largest sequencer input file. This size depends on the number of
explicit message transfers to be performed. The sequencer length may
be expanded or reduced for run mode. It is imperative that the
corresponding file that serves as the source of the sequencer’s input
file, N10, must be modified accordingly.

File Data Values

Prior to running the sample ladder, the sequencer initialization file
needs to be loaded with the numbers that correspond to the explicit
message transfer sequence. The following is a list of each mode’s
initialization file and the required/possible numbers to be stored in

Table C.8 Data Files

Data File
Address

Number of
Elements

Description

N9

1

N9:0 Sequencer Output

N10

Variable

N10:0 Sequencer Input

R6:0

Sequencer Control

Message Read Data Table Locations

(Control/Data)

N20 / F30

14

Voltage/Current Data

N21 / F31

13

Real-Time Power

N22 / F32

13

Power Factor

N23 / N33

23

KWh and KVAh

N24 / N34

23

KVarh

N25 / F35

10

Demand

N26 / N36

27

Diagnostic

IMPORTANT

Failure to modify the length of file N10 for a
modification of either the Configuration or Run
sequence results in improper operation of the ladder
program, and possible FAULT of the processor due to
invalid indirect offsets.