Powermonitor 3000 Data Tables A-31

Table A.21 Trend Log Configuration/Read-Back Record Select

CSP File No.

N24

Remote I/O BT

34

CIP Assy. Inst.

26 (Write), 27 (Read)

No. of Elements

26

User Configurable No

Data Type

Integer

Data Access

Read / Write

PM3000 Type

All

Element
No.

Modbus
Address

Element name

Range

Default
Value

Comment

0

40801

Password

0 to 9999

0

Required for configuration, -1 for readback select, returns -1.

1

40802

DeviceNet unique write
identifier

-32768 to
32767

0

Refer to DeviceNet Unique Write Identifier on page 4-36.

2

40803

Reserved

0

0

Must be 0 on a write; returns 0

3

40804

Read-back mode

0 to 6

2

Refer to Setting up the Trend Log on page 7-11, and Reading
Data from the Trend Log on page 7-12.

4

40805

Logging interval

-1 to 3600

900
(15 min)

Expressed in seconds
-1 = synchronize logging with demand interval
0 = disable periodic logging

5

40806

Logging mode

0 to 1

0

0 = Overwrite
1 = Fill and hold

6

40807

Clear trend log command

0 to 1

0

0 = no action
1 = clear trend log; returns 0

7

40808

Total records logged x 1000

0 to 999

-

Number of records = element 7 x 1000 + element 8

8

40809

Total records logged x 1

0 to 999

-

9

40810

Reserved

0

-

Must be 0 on a write; returns 0

10

40811

Parameter #1 selection

1 to 301

122

Refer to Setting up the Trend Log on page 7-11.
Defaults:
Parameter 1: 122, Net Kilowatt-hours
Parameter 2: 126, Net kVAR-hours
Parameter 3: 100, Demand watts

11

40812

Parameter #2 selection

0 to 301

126

12

40813

Parameter #3 selection

100

13

40814

Parameter #4 selection

0

14

40815

Parameter #5 selection

15

40816

Parameter #6 selection

16

40817

Parameter #7 selection

17

40818

Parameter #8 selection

18

40819

Parameter #9 selection

(1)

0 to 301

0

19

40820

Parameter #10 selection

20

40821

Parameter #11 selection

21

40822

Parameter #12 selection

22

40823

Parameter #13 selection

23

40824

Parameter #14 selection

24

40825

Parameter #15 selection

25

40826

Parameter #16 selection

(1) For DeviceNet Powermonitors you may configure parameters 9 through 16 but Table A.22 will return only the first 8 parameters.