Discrete data, Table a.3 – Rockwell Automation 1404-M4_M5_M6_M8 Powermonitor 3000 User Manual, PRIOR to Firmware rev. 3.0 User Manual

Page 180

Advertising
background image

Publication 1404-UM001D-EN-E - October 2004

A-6 Powermonitor 3000 Data Tables

Table A.3 Discrete Data

CSP File No.

N9

Remote I/O BT

10

CIP Assy. Inst.

3

No. of Elements

6

User Configurable No

Data Type

Integer

Data Access

Read Only

PM3000 Type

All

Element
No.

Modbus
Address

Element name

Range

Comment

0

30001

Relay output status

0 to 3

0 = De-energized & not forced
1 = Energized & not forced
2 = Force De-energized
3 = Force Energized

1

30002

Solid-state KYZ output
status

2

30003

Alarm output word

0 to FFFF Bitfield indicating state of the 16 alarm output flags; 0 = released, 1 = asserted.

Bit 0 = relay/setpoint output flag 1
Bit 1 = KYZ/setpoint output flag 2
Bit 2 = setpoint output flag 3

Bit 15 = setpoint output flag 16

3

30004

Status inputs state

0 to 3

Bit 0 = status input #1; 0 = open, 1 = contact closure detected
Bit 1 = status input #2; 0 = open, 1 = contact closure detected
Bit 2 = demand sync timeout; 1 = the demand delay expired before the next
expected external demand sync. This bit clears when the next external demand
sync occurs. Refer to Table A.6 Advanced Device Configuration element 23.
Bits 3-15 = unused (always 0)

4

30005

Status input #1 counter

0 to
29999

Counts to 29,999,rolls over to 0

5

30006

Status input #2 counter