Configuring the event log using communications – Rockwell Automation 1404-M4_M5_M6_M8 Powermonitor 3000 User Manual, PRIOR to Firmware rev. 3.0 User Manual

Page 136

Advertising
background image

Publication 1404-UM001D-EN-E - October 2004

7-4 Data Logging

Configuring the Event Log Using Communications

You may configure the Event Log by performing a valid table write to
Table A.26 Event Log Configuration/Read-Back Record Select. This
read/write data table contains these 6 integer elements:

Password: A valid password is required to set configuration

options or -1 to select a record for read-back

DeviceNet unique write identifier
Read-back mode: see below
Status input logging: 0 disables; 1 enables
Number of events logged: this read-only element is ignored on a

write

Time/date set logging: 0 disables; 1 enables

Table 7.2 Status Error Codes

Bits Hex

Description

bit 0

0001h

Master Module code flash status

bit 1

0002h

Master Module data flash status

bit 2

0004h

Master Module RAM Status

bit 3

0008h

Reserved for factory use

bit 4

0010h

Master Module NVRAM status

bit 5

0020h

Master Module data acquisition status

bit 6

0040h

Master Module real time clock status

bit 7

0080h

Reserved for factory use

bit 8

0100h

Reserved for factory use

bit 9

0200h

Display Module status

bit 10

0400h

Master Module watchdog timer status

bit 11

0800h

Master Module optional communications status

bit 12-15

1000h
-8000h

Reserved for factory use