Df1 pccc diagnostic status reply, Table a.17 – Rockwell Automation 1404-M4_M5_M6_M8 Powermonitor 3000 User Manual, PRIOR to Firmware rev. 3.0 User Manual

Page 199

Advertising
background image

Publication 1404-UM001D-EN-E - October 2004

Powermonitor 3000 Data Tables A-25

18

30619

Digital board revision

0 to 7

0 = 02A, 1 = 03A, etc.

19

30620

Analog board revision

0 to 7

0 = 02A, 1 = 03A, etc.

20

30621

Reserved

0

Returns 0

21

30622

Reserved 0

Returns

0

22

30623

MM Device ID

0 to 255

Sequentially assigned at time of manufacture. May not be
changed.

23

30624

Master Module type, current

4,5,6,or 8

4 = M4, 5 = M5, 6 = M6, 8 = M8; reflects any upgrades

24

30625

Display module type

0 to 1

0 = No display module connected
1 = 1404-DM connected to master module

25

30626

Option communications type

-

00 = No optional communications (native RS-485 only)
81 = DeviceNet V1
82 = ControlNet
84 = Remote I/O
85 = Ethernet Series A
86 = RS-232
88 = DeviceNet V2
89 = IEC870 comm card
90 = Ethernet Series B

26

30627

Accuracy Class

0 to 2

Indicates revenue metering accuracy class as manufactured
(refer to page 3-3).
0 = Class 1
1 = Class 0.5
2 = Class 0.2

Element
No.

Modbus
Address

Element name

Range

Comment

TIP

This is not truly a data table, but a reply to a PCCC
diagnostic status request (used by RSWho to display
text and an icon for the Powermonitor 3000). This
data is not accessible using Modbus.

Table A.17 DF1 PCCC Diagnostic Status Reply

Byte

Bits

Contents

Description

1

0-1

Mode/status

Unused

2-3

4-7

2

0-7

Type extender

EE

3

0-7

Extended interface type

36h = DF1 half-duplex slave (via native RS485 port or RS-232 port)
65h = Ethernet

4

0-7

Extended processor type

8Ah; 1404 Powermonitor 3000 products

5

0-4

Series/revision

Unused

5-7

6-16

All

Catalog number

(in ASCII)

Catalog number written into the device at time of production or calibration.
For example ‘1404-M4-05-A-RIO’

17-24

All

Product Specific

Unused