Publication 1404-UM001D-EN-E - October 2004

Data Logging 7-11

Setting up the Trend Log

You configure the Trend Log by performing a table write to
Table A.21 with the desired configuration settings. This read/write
data table contains 26 integer elements including:

Password: Required to configure logging, you may use -1 for

read-back selection

• DeviceNet unique write identifier
Read-back mode: See below; must be a valid entry even if

read-back is not being selected at this time

Logging interval: Interval in seconds (1 to 3,600). 0 disables

logging but does not disable setpoint-triggered logging; -1
synchronizes logging with demand interval.

Logging mode: 0 selects overwrite mode; 1 selects fill and hold.
Clear log command: 0 takes no action; 1 clears the trend log.
Parameter selections: You may select up to 16 parameters from

the list in Table A.59 to be logged. An entry of 0 selects no
parameter; only parameters preceding the first 0 in the table will
be logged.

Reserved elements: Must be 0
Total records logged: These read-only elements are ignored

during a write

The Powermonitor 3000 clears the trend log when you change any
parameter or the logging interval.

You may perform a simple table read of Table A.21 to view the
existing Trend Log configuration. When you read this table, the
password element returns a value of -1 and the reserved and
command elements return a value of 0. Elements 7 and 8 return the
Total Records Logged * 1000 and * 1 respectively.

TIP

Although you may configure up to 16 Trend Log
parameters on units with optional DeviceNet
communications, the results table will return only the
first 8.