Publication 1404-UM001D-EN-E - October 2004

3-8 Powermonitor 3000 Operations

Figure 3.1 Explanation of Power Factor Values

Energy Results

The Powermonitor 3000 calculates energy values including kWh
forward, reverse and net; kVAh; kVARh forward, reverse and net; and
kAh. You may read these values using the Display Module or via
communications.

Phase 1 Distortion Power Factor

The ratio between the magnitude of the
fundamental and the sum of the magnitudes for
all of the current harmonics for an individual
phase or all three phases.

0 to 100

Percent

Phase 2 Distortion Power Factor

Phase 3 Distortion Power Factor

Total Distortion Power Factor

Phase 1 Displacement Power Factor

The cosine of the phase angle between the
fundamental voltage and current for an
individual phase or all three phases; signed to
show lead (+) or lag (-).

-100 to 100

Percent

Phase 2 Displacement Power Factor

Phase 3 Displacement Power Factor

Total Displacement Power Factor

Table 3.4 Power and Power Factor Results

Parameter Description

Range

Units

I

IV

II

III

90˚

270˚

180˚

Pf = 0
+kVAR (Import)
kVARHR-F (Forward)

Pf = 0
-kVAR (Export)
kVARHR-R (Reverse)

Pf = 100%
+kW (Import)
kWH-F (Forward)

Pf = 100%
-kW (Export)
kWH-R (Reverse)

(Power Factor
Lagging)
(-)

(Power Factor
Leading)
(+)

(Power Factor
Lagging)
(-)

(Power Factor
Leading)
(+)