A-24 Powermonitor 3000 Data Tables

Table A.16 Selftest/Diagnostic Results

CSP File No.

N22

Remote I/O BT

36

CIP Assy. Inst.

23

No. of Elements

27

User Configurable No

Data Type

Integer

Data Access

Read only

PM3000 Type

All

Element
No.

Modbus
Address

Element name

Range

Comment

0

30601

Bulletin number

1404

1

30602

Series

0 to 8

0 = A, 1 = B, etc.

2

30603

Overall status

-

0 = OK

3

30604

Data Acquisition status

-

0 = OK
bit 0 = overall status; 0 = pass, 1 = fail
bit 1 = reserved
bit 2 = data bus connection failure
bit 3 = address test failure

4

30605

Data FLASH status

-

0 = OK

5

30606

Real-time clock status

-

0 = OK

6

30607

RTC NVRAM status

-

0 = OK
Non-zero indicates corruption of non-volatile memory. This
does not cause product to shutdown. The error is cleared on a
reset/power cycle. If this error is detected, date/time, and
energy values are reset.

7

30608

Option communications status -

0 = OK or no optional communications present

8

30609

Display module status

-

0 = OK or no DM connected

9

30610

Watchdog status

-

0 = OK

10

30611

Code FLASH status

-

0 = OK
bit 0 = overall status; 0 = pass, 1 = fail
bit 1 = boot code checksum failure
bit 2 = application code checksum failure
bit 3 = calibration CRC failure
bit 4 = no calibration data
bit 5 = wrong application firmware loaded

11

30612

RAM status

-

0 = OK
bit 0 = read/write test failure

12

30613

Application FRN

0 to 9999

100 indicates V1.00, 103 indicates V1.03, etc.

13

30614

Boot code FRN

0 to 9999

100 indicates V1.00, 101 indicates V1.01, etc.

14

30615

ASIC build #

0 to 9999

Revision number of the ‘code’ which was used to fabricate the
ASIC.

15

30616

Option communications FRN

0 to 9999

100 indicates V1.00, 103 indicates V1.03, etc. 0 = none (catalog
numbers ending in -000, -232)

16

30617

Display module FRN

0 to 9999

104 indicates V 1.04, 105 indicates V1.05, etc.
Returns 0 if no DM connected

17

30618

Reserved 0

Returns

0