Publication 1404-UM001D-EN-E - October 2004

3-12 Powermonitor 3000 Operations

Display Module
Functionality

The Display Module is a simple terminal that allows you to easily view
metering parameters or change configuration items. The Display
Module uses three modes of operation.

Display mode allows you to view Powermonitor 3000

parameters including metering, setpoint, min/max log, event log
and self-test information. You may also select a default screen to
be displayed at power-up or after 30 minutes without key
activity.

Program mode allows you to change configuration parameters,

with security against unauthorized configuration changes. Each
Powermonitor 3000 is password protected. In Program Mode,
the Display Module phase indicators (L1,L2,L3,N) flash.

Edit mode allows you to modify the selected parameters. In Edit

mode, the parameter being modified flashes, and the phase
indicators (L1,L2,L3,N) remain solid.

Demand Kilo-VARs

The calculated demand for reactive power.

0 to 999.9x10

21

kVAR

Max Demand Kilo-VARs

The maximum (peak) demand for reactive power
(included in Min/Max Log)

Demand Kilo-VA

The calculated demand for apparent power.

0 to 999.9x10

21

kVA

Max Demand Kilo-VA

The maximum (peak) demand for apparent power
(included in Min/Max Log)

Projected Current Demand

(1)

The projected demand for average current

0 to 999.9x10

21

Amps

Projected Kilo-Watt Demand

(1)

The projected demand for real power

0 to 999.9x10

21

kWatts

Projected Kilo-VAR Demand

(1)

The projected demand for reactive power

0 to 999.9x10

21

kVARs

Projected Kilo-VA Demand

(1)

The projected demand for apparent power

0 to 999.9x10

21

kVA

(1) Values returned depend on user selection of projected demand type in Advanced Configuration.

Table 3.5 Energy and Demand Results

Parameter Description

Range

Units