Metering power factor results, Table a.13 – Rockwell Automation 1404-M4_M5_M6_M8 Powermonitor 3000 User Manual, PRIOR to Firmware rev. 3.0 User Manual

Page 195

Advertising
background image

Publication 1404-UM001D-EN-E - October 2004

Powermonitor 3000 Data Tables A-21

Table A.13 Metering Power Factor Results

CSP File No.

F19

Remote I/O BT

33

CIP Assy. Inst.

18

No. of Elements

13

User Configurable No

Data Type

Floating point

Data Access

Read only

PM3000 Type

All

Element
No.

Modbus
Address

Element name

Units

Range

Comment

0

30501-02 L1 True Power Factor

Percent

-100 to 100

Ratio between power and apparent power.
+ = Lead
- = Lag

1

30503-04 L2 True Power Factor

-100 to 100

2

30505-06 L3 True Power Factor

-100 to 100

3

30507-08 3-phase True PF

-100 to 100

4

30509-10 L1 Displacement Power Factor

-100 to 100

Cosine of the phase angle between the fundamental
voltage and current.
+ = Lead
- = Lag

5

30511-12 L2 Displacement Power Factor

-100 to 100

6

30513-14 L3 Displacement Power Factor

-100 to 100

7

30515-16 3-phase Displacement PF

-100 to 100

8

30517-18 L1 Distortion Power Factor

0 to 100

The ratio between the magnitude of the fundamental
and the sum of the magnitudes for all of the current
harmonics.

9

30519-20 L2 Distortion Power Factor

0 to 100

10

30521-22 L3 Distortion Power Factor

0 to 100

11

30523-24 3-phase Distortion PF

0 to 100

12

30525-26 Metering iteration

-

0 to 32767

Increments by 1 to 32767, rolls over to 0