Publication 1404-UM001D-EN-E - October 2004

Powermonitor 3000 Data Tables A-39

Table A.29 List of Event Types

Applies to:

Table A.27 Event Log Results

PM3000 Type

See table

Event
Code.

M4
M5

M
6

M
8

Event type

Event Command
Code

Comment

0

• • No event

0

The log starts with no events recorded

1

• • Setpoint triggered

Setpoint Number

A setpoint activated

2

• • Setpoint released

A previously active setpoint released

3

• • Relay force energized

Relay Number

1 = Form C relay, 2 = KYZ

4

• • Relay force de-energized

5

• • Relay force released

6

• • Status input set

Status Input Number

7

• • Status input cleared

8

• • KWh counter set or cleared

1

Records command action

8

• • KVARh counter set or cleared

2

8

• • KVAh counter set or cleared

3

8

• • Ah counter set or cleared

4

8

• • All energy counters cleared

5

8

• • Trend log cleared

6

8

• • Min/max log cleared

7

8

• • Factory defaults restored

8

8

• • Status input #1 counter cleared

9

8

• • Status input #2 counter cleared

10

8

• • Reserved

11

8

• • Single setpoint timer cleared

12

8

• • All setpoint timers cleared

13

9

• • Power-up

0

Control power was applied.

10

• • Power-down

0

Control power was lost or internal reset occurred.

11

• • Selftest failure

Status Error Code

Refer to Table A.28 Status Error Codes (bitfield)

12

• • Date/time set

0

The date and/or time was set or altered.

13

• • Change of non-setpoint config data 0

14

• • Change of setpoint config data

0

15

• • NVRAM Clr

0

NVRAM has been cleared due to an extended loss
of control power or internal error.

16

• Transient detected

17

• User Comment

User has manually entered a comment to record the
impact of an event on your plant or process.

18

• • External Demand Sync Timeout

The demand delay expired before the next expected
external demand sync

19

• • Comm Card Reset

An unexpected comm card condition has been
detected and the master module has reset the
comm card in an attempt to resume normal
operation.