Trend log results, Table a.22, Table a.22 w – Rockwell Automation 1404-M4_M5_M6_M8 Powermonitor 3000 User Manual, PRIOR to Firmware rev. 3.0 User Manual

Page 206

Advertising
background image

Publication 1404-UM001D-EN-E - October 2004

A-32 Powermonitor 3000 Data Tables

Table A.22 Trend Log Results

CSP File No.

F25

Remote I/O BT

48

CIP Assy. Inst.

28

No. of Elements

14 (DeviceNet only), 22 (All other communications types)

User Configurable Yes

Data Type

Floating Point

Data Access

Read only

PM3000 Type

All

Element
No.

Modbus
Address

Element name

Range

Comment

0

30701-02

Reserved

0

Returns 0

1

30703-04

Internal Identifier

0 to 15

Increment from 1 to 15 for each record, rolls to 0

2

30705-06

Timestamp;

Year

Month/Date

Hour/minute

Seconds/hsec

1998 to 2097

Date and time record was recorded. Refer to Expressing Data in
Data Tables on page 4-18

3

30707-08

0101 to 1231

4

30709-10

0000 to 2359

5

30711-12

0000 to 5999

6

30713-14

User selected parameter #1

-

The values of parameters that were configured.

7

30715-16

User selected parameter #2

-

8

30717-18

User selected parameter #3

-

9

30719-20

User selected parameter #4

-

10

30721-22

User selected parameter #5

-

11

30723-24

User selected parameter #6

-

12

30725-26

User selected parameter #7

-

13

30727-28

User selected parameter #8

-

14

30729-30

User selected parameter #9

-

15

30731-32

User selected parameter #10

-

16

30733-34

User selected parameter #11

-

17

30735-36

User selected parameter #12

-

18

30737-38

User selected parameter #13

-

19

30739-40

User selected parameter #14

-

20

30741-42

User selected parameter #15

-

21

30743-44

User selected parameter #16

-