4-34 Communications

The example above is a ControlLogix message instruction to read the
user-configured table, assembly instance 37.

Up to four concurrent explicit messaging connections are supported
by the DeviceNet communications port.

DeviceNet Message Types

The Powermonitor 3000 supports the following message types:

TIP

Because the floating-point word order in the
ControlLogix controller is reversed from that in the
Powermonitor 3000, your ladder logic will need to
reverse the word order so the data may be
interpreted correctly. The SWPB instruction performs
this function.

Table 4.7 DeviceNet Message Types

Group

CAN Identifier
Field

Message Type

1

01101xxxxxx

Slave’s I/O COS or Cyclic message

01111xxxxxx

Slave’s I/O poll response or COS / Cyclic ACK message