Publication 1404-UM001D-EN-E - October 2004

Communications 4-11

4. Edit the Scanner List

The DeviceNet scanner needs to know how the information is
coming from the Powermonitor 3000. Select the Scan List tab
and move the Powermonitor 3000 into the Scanlist set.

5. Edit the Data Table Map

The DeviceNet scanner needs to know which bytes will be
scanned from the Powermonitor 3000. Select the Input tab.

This allows the user to determine where the information is
stored inside the scanner module. When finished configuring,
select the Apply button.

6. Download Configuration to the Scanner

All of the configuration data must be downloaded to the scanner
module. Select the Save to SDN button, download All Records,
and allow the scanner to reset.

Afterwards, the DeviceNet Scanner displays an 80, followed by a
00 when everything is configured properly.