Basler Electric DGC-2020HD Modbus Protocol User Manual

Page 111

Advertising
background image

9469300991 Rev A

105

DGC-2020HD Modbus

™ Protocol

Default Register Table

Name

Description

Group Register Type Bytes R/W

Unit

Range

I Aux=55
Gen kW A=56

Gen kW B=57

Gen kW C=58
Gen kW Total=59

Bus 1 kW A=60
Bus 1 kW B=61

Bus 1 kW C=62
Bus 1 kW Total=63

Bus 2 kW A=64

Bus 2 kW B=65
Bus 2 kW C=66

Bus 2 kW Total=67
Gen kVA A=68

Gen kVA B=69
Gen kVA C=70

Gen kVA Total=71

Bus 1 kVA A=72
Bus 1 kVA B=73

Bus 1 kVA C=74
Bus 1 kVA Total=75

Bus 2 kVA A=76
Bus 2 kVA B=77

Bus 2 kVA C=78

Bus 2 kVA Total=79
Gen kvar A=80

Gen kvar B=81
Gen kvar C=82

Gen kvar Total=83
Bus 1 kvar A=84

Bus 1 kvar B=85
Bus 1 kvar C=86

Bus 1 kvar Total=87

Bus 2 kvar A=88
Bus 2 kvar B=89

Bus 2 kvar C=90
Bus 2 kvar Total=91

Fuel Pressure=92
Injector metering rail

pressure=93

Total Fuel Used=94
Fuel temperature=95

Engine oil temperature=96
Engine intercooler

temperature=97
Coolant pressure=98

Fuel Rate=99

Boost pressure=100
Intake manifold

temperature=101
Charge air temperature=102

Engine Percent Load=103
Analog Input 1=104

Analog Input 2=105
Analog Input 3=106

Analog Input 4=107

kW Load Percent=108
Number of Units Online=109

System kW Capacity=110
System Total Gen kW=111

System Total Gen kvar=112
AEM 1 Analog Input 1=300

AEM 1 Analog Input 2=301

AEM 1 Analog Input 3=302
AEM 1 Analog Input 4=303

AEM 1 Analog Input 5=304
AEM 1 Analog Input 6=305

AEM 1 Analog Input 7=306
AEM 1 Analog Input 8=307

AEM 1 RTD Input 1=308

AEM 1 RTD Input 2=309
AEM 1 RTD Input 3=310

AEM 1 RTD Input 4=311
AEM 1 RTD Input 5=312

AEM 1 RTD Input 6=313
AEM 1 RTD Input 7=314

AEM 1 RTD Input 8=315

AEM 1 TC Input 1=316
AEM 1 TC Input 2=317

AEM 2 Analog Input 1=318
AEM 2 Analog Input 2=319

AEM 2 Analog Input 3=320