Basler Electric DGC-2020HD Modbus Protocol User Manual

Page 51

Advertising
background image

9469300991 Rev A

45

DGC-2020HD Modbus

™ Protocol

Default Register Table

Name

Description

Register Bit Type Bytes R/W

Range

ECU Config

High Exhaust Temp A Pre-Alarm

1111

0

Uint16 2

R

False=0 True=1

ECU Config

High Exhaust Temp B Pre-Alarm

1111

1

Uint16 2

R

False=0 True=1

ECU Config

High Fuel Temp Pre-Alarm

1111

2

Uint16 2

R

False=0 True=1

ECU Config

High Storage Tank Level Pre-Alarm

1111

3

Uint16 2

R

False=0 True=1

ECU Config

High Voltage Supply Pre-Alarm

1111

4

Uint16 2

R

False=0 True=1

ECU Config

Hi Pressure IN 1 Pre-Alarm

1111

5

Uint16 2

R

False=0 True=1

ECU Config

Hi Pressure IN 2 Pre-Alarm

1111

6

Uint16 2

R

False=0 True=1

ECU Config

Hi T Ambient Pre-Alarm

1111

7

Uint16 2

R

False=0 True=1

ECU Config

Hi TCOIL 1 Pre-Alarm

1111

8

Uint16 2

R

False=0 True=1

ECU Config

Hi TCOIL 2 Pre-Alarm

1111

9

Uint16 2

R

False=0 True=1

ECU Config

Hi TCOIL 3 Pre-Alarm

1111

10 Uint16 2

R

False=0 True=1

ECU Config

Idle Speed Low Pre-Alarm

1111

11 Uint16 2

R

False=0 True=1

ECU Config

Load Gen On Status

1111

12 Uint16 2

R

False=0 True=1

ECU Config

Low Charge Air Coolant Level Pre-Alarm

1111

13 Uint16 2

R

False=0 True=1

ECU Config

Low Day Tank Level Pre-Alarm

1111

14 Uint16 2

R

False=0 True=1

ECU Config

Low ECU Supply Voltage Pre-Alarm

1111

15 Uint16 2

R

False=0 True=1

ECU Config

Low Storage Tank Level Pre-Alarm

1112

0

Uint16 2

R

False=0 True=1

ECU Config

Low Voltage Supply Pre-Alarm

1112

1

Uint16 2

R

False=0 True=1

ECU Config

Preheat Temp Not Reached Status

1112

2

Uint16 2

R

False=0 True=1

ECU Config

Priming Fault Pre-Alarm

1112

3

Uint16 2

R

False=0 True=1

ECU Config

Priming Pump On Status

1112

4

Uint16 2

R

False=0 True=1

ECU Config

Run-up Speed Low Pre-Alarm

1112

5

Uint16 2

R

False=0 True=1

ECU Config

Speed DEC Feedback Status

1112

6

Uint16 2

R

False=0 True=1

ECU Config

Speed Demand Fail Mode Status

1112

7

Uint16 2

R

False=0 True=1

ECU Config

Speed Demand Fail Pre-Alarm

1112

8

Uint16 2

R

False=0 True=1

ECU Config

Speed INC Feedback Status

1112

9

Uint16 2

R

False=0 True=1

ECU Config

Start Speed Low Pre-Alarm

1112

10 Uint16 2

R

False=0 True=1

ECU Config

T Alternator Wiring Pre-Alarm

1112

11 Uint16 2

R

False=0 True=1

Settings Group

Use SG0

1112

12 Uint16 2

R

False=0 True=1

Settings Group

Use SG1

1112

13 Uint16 2

R

False=0 True=1

Settings Group

Use SG2

1112

14 Uint16 2

R

False=0 True=1

Settings Group

Use SG3

1112

15 Uint16 2

R

False=0 True=1

Sync

Active

1113

0

Uint16 2

R

False=0 True=1

Sync

Breaker Close OK

1113

1

Uint16 2

R

False=0 True=1

Sync

Volt OK

1113

2

Uint16 2

R

False=0 True=1

Sync

Freq OK

1113

3

Uint16 2

R

False=0 True=1

Sync

Phase OK

1113

4

Uint16 2

R

False=0 True=1

Sync

Sync OK

1113

5

Uint16 2

R

False=0 True=1

Generator Breaker

Breaker Status

1113

6

Uint16 2

R

False=0 True=1

Generator Breaker

Sync Fail

1113

7

Uint16 2

R

False=0 True=1

Generator Breaker

Fail to Close

1113

8

Uint16 2

R

False=0 True=1

Generator Breaker

Fail to Open

1113

9

Uint16 2

R

False=0 True=1

Mains Breaker

Breaker Status

1113

10 Uint16 2

R

False=0 True=1

Mains Breaker

Sync Fail

1113

11 Uint16 2

R

False=0 True=1

Mains Breaker

Fail to Close

1113

12 Uint16 2

R

False=0 True=1

Mains Breaker

Fail to Open

1113

13 Uint16 2

R

False=0 True=1

Breaker Local Request Generation

Mains Fail Transfer Inhibit From PLC

1113

14 Uint16 2

R

False=0 True=1

Breaker Local Request Generation

Closed Transition Override From PLC

1113

15 Uint16 2

R

False=0 True=1

Breaker Local Request Generation

Mains Fail Test Active

1114

0

Uint16 2

R

False=0 True=1

Breaker Local Request Generation

Auto Breaker OP Inhibit

1114

1

Uint16 2

R

False=0 True=1

Breaker Local Request Generation

Mains Fail Transfer Enabled

1114

2

Uint16 2

R

False=0 True=1

Breaker Local Request Generation

Mains Fail Transfer Fail

1114

3

Uint16 2

R

False=0 True=1

Breaker Local Request Generation

Mains Fail Transfer Complete

1114

4

Uint16 2

R

False=0 True=1

Breaker Local Request Generation

Mains Zero Power Flow

1114

5

Uint16 2

R

False=0 True=1

Genset Controller

Gen Reverse Rotation

1114

6

Uint16 2

R

False=0 True=1

Genset Controller

Bus 1 ReverseRotation

1114

7

Uint16 2

R

False=0 True=1

Genset Controller

Bus 2 ReverseRotation

1114

8

Uint16 2

R

False=0 True=1

Bias Control

Take Over Load Active

1114

9

Uint16 2

R

False=0 True=1

Bias Control

var Mode Active

1114

10 Uint16 2

R

False=0 True=1

Bias Control

PF Mode Active

1114

11 Uint16 2

R

False=0 True=1

Gen Condition

Dead

1114

12 Uint16 2

R

False=0 True=1

Gen Condition

Failed

1114

13 Uint16 2

R

False=0 True=1

Gen Condition

Stable

1114

14 Uint16 2

R

False=0 True=1

Bus 1 Condition

Dead

1114

15 Uint16 2

R

False=0 True=1

Bus 1 Condition

Failed

1115

0

Uint16 2

R

False=0 True=1

Bus 1 Condition

Stable

1115

1

Uint16 2

R

False=0 True=1

Bus 2 Condition

Dead

1115

2

Uint16 2

R

False=0 True=1

Bus 2 Condition

Failed

1115

3

Uint16 2

R

False=0 True=1

Bus 2 Condition

Stable

1115

4

Uint16 2

R

False=0 True=1

Coolant Temp Sender Fail

Alarm

1115

5

Uint16 2

R

False=0 True=1

Coolant Temp Sender Fail

Pre-Alarm

1115

6

Uint16 2

R

False=0 True=1

Oil Pressure Sender Fail

Alarm

1115

7

Uint16 2

R

False=0 True=1

Oil Pressure Sender Fail

Pre-Alarm

1115

8

Uint16 2

R

False=0 True=1

Fuel Level Sender Fail

Alarm

1115

9

Uint16 2

R

False=0 True=1

Fuel Level Sender Fail

Pre-Alarm

1115

10 Uint16 2

R

False=0 True=1