Legacy register table, Breaker management – Basler Electric DGC-2020HD Modbus Protocol User Manual

Page 235

Advertising
background image

9469300991 Rev A

229

DGC-2020HD Modbus

™ Protocol

Legacy Register Table

Legacy Register Table

The DGC-2020HD maps all legacy parameters previously associated with the DGC-2020 into the Holding
Register address space (4XXXXX). Query address N will access the Holding Register N+1. The Data
Format is Integer type data unless identified otherwise in the Data Format column.

The register table on the following pages contains the following groups:

Breaker Management, Bias Control Settings, Pulse Outputs, Bus Condition Detection, Senders, System
Configuration and Status, Control, Communication, Protection, Alarms, and Metering.

Breaker Management

Register

Description

Type

Units

Scaling Factor

R/W

Range

42000

Gen Breaker Configured

Int32

n/a

n/a

RW

0 = Not Configured
1 = Configured

42002

Gen Breaker Open Pulse Time

Int32

Centisecond

Centi

RW

1 - 80

42004

Gen Breaker Close Pulse Time

Int32

Centisecond

Centi

RW

1 - 80

42006

Gen Breaker Contact Type

Int32

n/a

n/a

RW

0 = Pulse
1 = Continuous

42008

Gen Breaker Close Time

Int32

Millisecond

n/a

RW

0 - 800

42010

Reserved

42012

Mains Breaker Configured

Int32

n/a

n/a

RW

0 = Not Configured

1 = Configured

42014

Mains Breaker Open Pulse Time

Int32

Centisecond

Centi

RW

1 - 80

42016

Mains Breaker Close Pulse Time

Int32

Centisecond

Centi

RW

1 - 80

42018

Mains Breaker Output Continuous

Int32

n/a

n/a

RW

0 = Pulse

1 = Continuous

42020

Mains Breaker Close Time

Int32

Millisecond

n/a

RW

0 - 800

42022

Reserved

42024

Synchronizer Type

Int32

n/a

n/a

RW

1 = Anticipatory
2 = Phase Lock Loop

42026

Synchronizer Mode

Int32

n/a

n/a

RW

0 = Off Mode
1 = Auto Mode

42028

Slip Frequency

Int32

CentiHertz

Centi

RW

1 - 50

42030

Breaker Closing Angle

Int32

DeciDegree

Deci

RW

30 - 200

42032

Regulation Offset

Int32

DeciPercent

Deci

RW

20 - 150

42034

Vgen > Vbus

Int32

n/a

n/a

RW

0 = Disable

1 = Enable

42036

Fgen > Fbus

Int32

n/a

n/a

RW

0 = Disable
1 = Enable

42038-40

Reserved

42042

Breaker Close Wait Time

Float

Second

n/a

RW

0.1 - 600

42044

Sync Time Delay

Float

Second

n/a

RW

0.1 - 0.8

42046

Sync Fail Time Delay

Float

Second

n/a

RW

0.1 - 600

42048

Mains Fail Transfer Enable

Int32

n/a

n/a

RW

0 = Disable

1 = Enable

42050

Gen Breaker Status

Int32

n/a

n/a

R

0 = Open

1 = Closed

42052

Mains Breaker Status

Int32

n/a

n/a

R

0 = Open

1 = Closed

42054

Mains Fail Transfer Delay

Int32

Second

n/a

RW

0 - 300

42056

Mains Fail Return Delay

Int32

Second

n/a

RW

0 - 1800

42058

Mains Fail Max Transfer Time

Int32

Second

n/a

RW

1 - 120

42060

Reserved

42062

Dead Bus Close Enable

Int32

n/a

n/a

RW

0 = Disable

1 = Enable

42064

Sync Speed Gain

Float

n/a

n/a

RW

0.001 - 1000

42066

Sync Voltage Gain

Float

n/a

n/a

RW

0.001 - 1000

42068

Max Parallel Time

Int32

Second

Deci

RW

1 - 100000

42070

Mains Fail Transfer Type

Int32

n/a

n/a

RW

0 = Open

1 = Close

42072

In Phase Monitor Enable

Int32

n/a

n/a

RW

0 = Disable

1 = Enable

42074

Dead Gen Close Enable

Int32

n/a

n/a

RW

0 = Disable

1 = Enable

42076

Reserved

42078

Min Slip Control Limit

Int32

n/a

Centi

RW

0 - 200

42080

Max Slip Control Limit

Int32

n/a

Centi

RW

0 - 200

42082

Rev. Rotation Mains Fail Inhibit

Int32

n/a

n/a

RW

0 = Disable

1 = Enable