Basler Electric DGC-2020HD Modbus Protocol User Manual

Page 309

Advertising
background image

9469300991 Rev A

303

DGC-2020HD Modbus

™ Protocol

Legacy Register Table

Register

Description

Type

Units

Scaling

Factor

R/W

Range

46750

User Config Input 1 Config Type

Int32

n/a

n/a

RW 0 = Status Only

1 = Pre-Alarm

2 = Alarm

46752

User Config Input 1 Time Delay

Int32

Second

n/a

RW 0 – 300

46754

User Config Input 1 Engine Running Only

Int32

n/a

n/a

RW 0 = Always

1 = While Engine Running Only

46756

User Config Input 2 Config Type

Int32

n/a

n/a

RW 0 = Status Only

1 = Pre-Alarm

2 = Alarm

46758

User Config Input 2 Time Delay

Int32

Second

n/a

RW 0 – 300

46760

User Config Input 2 Engine Running Only

Int32

n/a

n/a

RW 0 = Always

1 = While Engine Running Only

46762

User Config Input 3 Config Type

Int32

n/a

n/a

RW 0 = Status Only

1 = Pre-Alarm

2 = Alarm

46764

User Config Input 3 Time Delay

Int32

Second

n/a

RW 0 – 300

46766

User Config Input 3 Engine Running Only

Int32

n/a

n/a

RW 0 = Always

1 = While Engine Running Only

46768

User Config Input 4 Config Type

Int32

n/a

n/a

RW 0 = Status Only

1 = Pre-Alarm
2 = Alarm

46770

User Config Input 4 Time Delay

Int32

Second

n/a

RW 0 – 300

46772

User Config Input 4 Engine Running Only

Int32

n/a

n/a

RW 0 = Always

1 = While Engine Running Only

46774

User Config Input 5 Config Type

Int32

n/a

n/a

RW 0 = Status Only

1 = Pre-Alarm
2 = Alarm

46776

User Config Input 5 Time Delay

Int32

Second

n/a

RW 0 – 300

46778

User Config Input 5 Engine Running Only

Int32

n/a

n/a

RW 0 = Always

1 = While Engine Running Only

46780

User Config Input 6 Config Type

Int32

n/a

n/a

RW 0 = Status Only

1 = Pre-Alarm
2 = Alarm

46782

User Config Input 6 Time Delay

Int32

Second

n/a

RW 0 – 300

46784

User Config Input 6 Engine Running Only

Int32

n/a

n/a

RW 0 = Always

1 = While Engine Running Only

46786

User Config Input 7 Config Type

Int32

n/a

n/a

RW 0 = Status Only

1 = Pre-Alarm
2 = Alarm

46788

User Config Input 7 Time Delay

Int32

Second

n/a

RW 0 – 300

46790

User Config Input 7 Engine Running Only

Int32

n/a

n/a

RW 0 = Always

1 = While Engine Running Only

46792

User Config Input 8 Config Type

Int32

n/a

n/a

RW 0 = Status Only

1 = Pre-Alarm
2 = Alarm

46794

User Config Input 8 Time Delay

Int32

Second

n/a

RW 0 – 300

46796

User Config Input 8 Engine Running Only

Int32

n/a

n/a

RW 0 = Always

1 = While Engine Running Only

46798

User Config Input 9 Config Type

Int32

n/a

n/a

RW 0 = Status Only

1 = Pre-Alarm

2 = Alarm

46800

User Config Input 9 Time Delay

Int32

Second

n/a

RW 0 – 300

46802

User Config Input 9 Engine Running Only

Int32

n/a

n/a

RW 0 = Always

1 = While Engine Running Only

46804

User Config Input 10 Config Type

Int32

n/a

n/a

RW 0 = Status Only

1 = Pre-Alarm

2 = Alarm

46806

User Config Input 10 Time Delay

Int32

Second

n/a

RW 0 – 300

46808

User Config Input 10 Engine Running Only

Int32

n/a

n/a

RW 0 = Always

1 = While Engine Running Only

46810

User Config Input 11 Config Type

Int32

n/a

n/a

RW 0 = Status Only

1 = Pre-Alarm

2 = Alarm

46812

User Config Input 11 Time Delay

Int32

Second

n/a

RW 0 – 300

46814

User Config Input 11 Engine Running Only

Int32

n/a

n/a

RW 0 = Always

1 = While Engine Running Only

46816

User Config Input 12 Config Type

Int32

n/a

n/a

RW 0 = Status Only

1 = Pre-Alarm

2 = Alarm

46818

User Config Input 12 Time Delay

Int32

Second

n/a

RW 0 – 300

46820

User Config Input 12 Engine Running Only

Int32

n/a

n/a

RW 0 = Always

1 = While Engine Running Only

46822

User Config Input 13 Config Type

Int32

n/a

n/a

RW 0 = Status Only

1 = Pre-Alarm

2 = Alarm

46824

User Config Input 13 Time Delay

Int32

Second

n/a

RW 0 – 300

46826

User Config Input 13 Engine Running Only

Int32

n/a

n/a

RW 0 = Always

1 = While Engine Running Only

Advertising