Basler Electric DGC-2020HD Modbus Protocol User Manual

Page 225

Advertising
background image

9469300991 Rev A

219

DGC-2020HD Modbus

™ Protocol

Default Register Table

Name

Description

Group Register Type Bytes R/W

Unit

Range

AEM 4 RTD Input 4=365
AEM 4 RTD Input 5=366

AEM 4 RTD Input 6=367

AEM 4 RTD Input 7=368
AEM 4 RTD Input 8=369

AEM 4 TC Input 1=370
AEM 4 TC Input 2=371

AVR Output=372
GOV Output=373

LS Output=374

Config Protection 5

Hysteresis

GG

24938

Float

4

R W Percent

0 - 100

Config Protection 5

Arming Delay

GG

24940

Float

4

R W Second

0 - 300

Config Protection 5

Threshold 1 Type

GG

24942

Int32

4

R W n/a

Disabled=0

Over=1
Under=2

Config Protection 5

Threshold 1 Pickup

GG

24944

Float

4

R W n/a

-999999 - 999999

Config Protection 5

Threshold 1 Activation Delay

GG

24946

Float

4

R W Second

0 - 300

Config Protection 5

Threshold 1 Alarm Configuration GG

24948

Uint32 4

R W n/a

Status Only=0

Pre-Alarm=1
Alarm=2

Config Protection 5

Threshold 2 Type

GG

24950

Int32

4

R W n/a

Disabled=0

Over=1

Under=2

Config Protection 5

Threshold 2 Pickup

GG

24958

Float

4

R W n/a

-999999 - 999999

Config Protection 5

Threshold 2 Activation Delay

GG

24960

Float

4

R W Second

0 - 300

Config Protection 5

Threshold 2 Alarm Configuration GG

24962

Uint32 4

R W n/a

Status Only=0
Pre-Alarm=1

Alarm=2

Config Protection 5

Threshold 3 Type

GG

24964

Int32

4

R W n/a

Disabled=0

Over=1
Under=2

Config Protection 5

Threshold 3 Pickup

GG

24966

Float

4

R W n/a

-999999 - 999999

Config Protection 5

Threshold 3 Activation Delay

GG

24968

Float

4

R W Second

0 - 300

Config Protection 5

Threshold 3 Alarm Configuration GG

24970

Uint32 4

R W n/a

Status Only=0

Pre-Alarm=1
Alarm=2

Config Protection 5

Threshold 4 Type

GG

24972

Int32

4

R W n/a

Disabled=0
Over=1

Under=2

Config Protection 5

Threshold 4 Pickup

GG

24974

Float

4

R W n/a

-999999 - 999999

Config Protection 5

Threshold 4 Activation Delay

GG

24976

Float

4

R W Second

0 - 300

Config Protection 5

Threshold 4 Alarm Configuration GG

24978

Uint32 4

R W n/a

Status Only=0
Pre-Alarm=1

Alarm=2

Config Protection 5

Low-Line Scale Current

GG

24980

Float

4

R W n/a

0.001 - 3

Config Protection 5

Low-Line Scale Voltage

GG

24982

Float

4

R W n/a

0.001 - 3

Config Protection 5

Label

GG

24984

String 16

R W n/a

0 - 16

Config Protection 6

Parameter Selection

GG

24986

Int32

4

R W n/a

No Parameter=0

Oil Pressure=1
Coolant Temp=2

Battery Volts=3
RPM=4

Fuel Level=5
Gen Hz=6

Gen VAB=7

Gen VBC=8
Gen VCA=9

Gen Vavg LL=10
Gen VAN=11

Gen VBN=12
Gen VCN=13

Gen Vavg LN=14

Bus 1 Hz=15
Bus 1 VAB=16

Bus 1 VBC=17
Bus 1 VCA=18

Bus 1 Vavg LL=19
Bus 1 VA=20

Bus 1 VB=21
Bus 1 VC=22

Bus 1 Vavg LN=23

Bus 2 Hz=24
Bus 2 VAB=25

Bus 2 VBC=26
Bus 2 VCA=27

Bus 2 Vavg LL=28
Bus 2 VAN=29

Bus 2 VBN=30

Bus 2 VCN=31
Bus 2 Vavg LN=32