Basler Electric DGC-2020HD Modbus Protocol User Manual

Page 234

Advertising
background image

228

9469300991 Rev A

Default Register Table

DGC-2020HD Modbus

™ Protocol

Name

Description

Group Register Type Bytes R/W

Unit

Range

Config Protection 8

Threshold 4 Type

GG

25122

Int32

4

R W n/a

Disabled=0
Over=1

Under=2

Config Protection 8

Threshold 4 Pickup

GG

25124

Float

4

R W n/a

-999999 - 999999

Config Protection 8

Threshold 4 Activation Delay

GG

25126

Float

4

R W Second

0 - 300

Config Protection 8

Threshold 4 Alarm Configuration GG

25128

Uint32 4

R W n/a

Status Only=0

Pre-Alarm=1
Alarm=2

Config Protection 8

Low-Line Scale Current

GG

25130

Float

4

R W n/a

0.001 - 3

Config Protection 8

Low-Line Scale Voltage

GG

25132

Float

4

R W n/a

0.001 - 3

Config Protection 8

Label

GG

25134

String 16

R W n/a

0 - 16