Protection settings – Basler Electric DGC-2020HD Modbus Protocol User Manual

Page 139

Advertising
background image

9469300991 Rev A

133

DGC-2020HD Modbus

™ Protocol

Default Register Table

Name

Description

Group Register Type Bytes R/W

Unit

Range

AEM 4 Metering

RTD Input 2 Raw Value

GG

10876

Float

4

R

Ohm

n/a

AEM 4 Metering

RTD Input 3 Raw Value

GG

10878

Float

4

R

Ohm

n/a

AEM 4 Metering

RTD Input 4 Raw Value

GG

10880

Float

4

R

Ohm

n/a

AEM 4 Metering

RTD Input 5 Raw Value

GG

10882

Float

4

R

Ohm

n/a

AEM 4 Metering

RTD Input 6 Raw Value

GG

10884

Float

4

R

Ohm

n/a

AEM 4 Metering

RTD Input 7 Raw Value

GG

10886

Float

4

R

Ohm

n/a

AEM 4 Metering

RTD Input 8 Raw Value

GG

10888

Float

4

R

Ohm

n/a

AEM 4 Metering

RTD Input 1 Scaled

Value

GG

10890

Float

4

R

Deg F

n/a

AEM 4 Metering

RTD Input 2 Scaled

Value

GG

10892

Float

4

R

Deg F

n/a

AEM 4 Metering

RTD Input 3 Scaled
Value

GG

10894

Float

4

R

Deg F

n/a

AEM 4 Metering

RTD Input 4 Scaled
Value

GG

10896

Float

4

R

Deg F

n/a

AEM 4 Metering

RTD Input 5 Scaled
Value

GG

10898

Float

4

R

Deg F

n/a

AEM 4 Metering

RTD Input 6 Scaled
Value

GG

10900

Float

4

R

Deg F

n/a

AEM 4 Metering

RTD Input 7 Scaled

Value

GG

10902

Float

4

R

Deg F

n/a

AEM 4 Metering

RTD Input 8 Scaled

Value

GG

10904

Float

4

R

Deg F

n/a

AEM 4 Metering

Thermal Input 1 Raw

Value

GG

10906

Float

4

R

Millivolt

n/a

AEM 4 Metering

Thermal Input 2 Raw

Value

GG

10908

Float

4

R

Millivolt

n/a

AEM 4 Metering

Analog Output 1 Raw

Value

GG

10910

Float

4

R

n/a

n/a

AEM 4 Metering

Analog Output 2 Raw
Value

GG

10912

Float

4

R

n/a

n/a

AEM 4 Metering

Analog Output 3 Raw
Value

GG

10914

Float

4

R

n/a

n/a

AEM 4 Metering

Analog Output 4 Raw
Value

GG

10916

Float

4

R

n/a

n/a

AEM 4 Metering

Analog Output 1 Scaled

Value

GG

10918

Float

4

R

n/a

n/a

AEM 4 Metering

Analog Output 2 Scaled

Value

GG

10920

Float

4

R

n/a

n/a

AEM 4 Metering

Analog Output 3 Scaled

Value

GG

10922

Float

4

R

n/a

n/a

AEM 4 Metering

Analog Output 4 Scaled

Value

GG

10924

Float

4

R

n/a

n/a

AEM 4 Metering

Thermal Input 1 Scaled

Value

GG

10926

Float

4

R

Deg F

n/a

AEM 4 Metering

Thermal Input 2 Scaled
Value

GG

10928

Float

4

R

Deg F

n/a

Protection Settings

Name

Description

Group Register Type Bytes R/W

Unit

Range

27P-1

Mode

SG0 1P 20000

Uint32 4

R W n/a

Disabled=0
Enabled=1

27P-1

Source

SG0 1P 20002

Uint32 4

R W n/a

Gen=0

Bus 1=1

Bus 2=2

27P-1

Pickup

SG0 1P 20004

Float

4

R W Volt

1 - 576

27P-1

Time Delay

SG0 1P 20006

Float

4

R W Millisecond 0 - 600000

27P-1

Alarm Configuration

SG0 1P 20008

Uint32 4

R W n/a

Status Only=0
Pre-Alarm=1

Alarm=2

27P-1

Low-Line Scale

SG0 1P 20010

Float

4

R W n/a

0.001 - 3

27P-1

Frequency Inhibit

SG0 1P 20012

Float

4

R W Hertz

20 - 90

27P-1

Mode

SG0 3P 20014

Uint32 4

R W n/a

Disabled=0
Enabled=1

27P-1

Source

SG0 3P 20016

Uint32 4

R W n/a

Gen=0

Bus 1=1

Bus 2=2

27P-1

Pickup

SG0 3P 20018

Float

4

R W Volt

1 - 576

27P-1

Time Delay

SG0 3P 20020

Float

4

R W Millisecond 0 - 600000

27P-1

Alarm Configuration

SG0 3P 20022

Uint32 4

R W n/a

Status Only=0
Pre-Alarm=1

Alarm=2

27P-1

Low-Line Scale

SG0 3P 20024

Float

4

R W n/a

0.001 - 3

27P-1

Frequency Inhibit

SG0 3P 20026

Float

4

R W Hertz

20 - 90