243

DGC-2020HD Modbus

™ Protocol

Legacy Register Table

Register

Description

Type

Units

Scaling Factor

R/W

Range

44464

1 Phase Overcurrent Curve

(51-3)

Uint32

n/a

n/a

RW

0 = S1 Curve

1 = S2 Curve
2 = L1 Curve

3 = L2 Curve
4 = D Curve

5 = M Curve
6 = I1 Curve

7 = I2 Curve

8 = V1 Curve
9 = V2 Curve

10 = E1 Curve
11 = E2 Curve

12 = A Curve
13 = B Curve

14 = C Curve

15 = G Curve
16 = F Curve

17 = Programmable

44466

1 Phase Overcurrent Alarm Configuration (51-3)

Uint32

n/a

n/a

RW

0 = None

1 = Alarm
2 = Pre-Alarm

3 = Status Only

44468

Overcurrent Low Line Scale Factor (51-3)

Float

n/a

n/a

RW

0.001 - 3

44470

3 Phase Overcurrent Reset Type (51-3)

Int32

n/a

n/a

RW

0 = Instantaneous
1 = Integrating

44472

1 Phase Overcurrent Reset Type (51-3)

Int32

n/a

n/a

RW

0 = Instantaneous
1 = Integrating

44474

51-3 Curve Constant A

Float

n/a

n/a

RW

0 - 600

44476

51-3 Curve Constant B

Float

n/a

n/a

RW

0 - 25

44478

51-3 Curve Constant C

Float

n/a

n/a

RW

0 - 1

44480

51-3 Curve Constant N

Float

n/a

n/a

RW

0.5 - 2.5

44482

51-3 Curve Constant R

Float

n/a

n/a

RW

0 - 30

44484

78 Vector Shift Alarm Config

Uint32

n/a

n/a

RW

0 = None
1 = Alarm

2 = Pre-Alarm
3 = Status Only

44486

78 Vector Shift Pickup

Int32

Degree

n/a

RW

2 - 90

44488

78 Open Mains Breaker on Trip

Int32

n/a

n/a

RW

0 = Disable

1 = Enable

44490

81 ROCOF Alarm Config

Uint32

n/a

n/a

RW

0 = None

1 = Alarm
2 = Pre-Alarm

3 = Status Only

44492

81 ROCOF Pickup

Uint32

Hz/Second

Deci

RW

2 - 100

44494

81 ROCOF Activation Delay

Uint32

Second

Milli

RW

0 - 10000

44496

81 ROCOF Open Mains Breaker on Trip

Int32

n/a

n/a

RW

0 = Disable
1 = Enable

44498

Alternate Frequency Scale Factor

Float

n/a

n/a

RW

0.001 - 100

Alarms

Register

Description

Type

Units

Scaling Factor R/W

Range

44500

High Coolant Temp Alarm Enable

Uint32 n/a

n/a

RW

0 = Disable

1 = Enable

44502

High Coolant Temp Alarm Threshold

Uint32 Deg F

n/a

RW

100 - 280

44504

Metric High Coolant Temp Alarm Threshold

Int32

Deg C

n/a

RW

38 - 138

44506

High Coolant Temp Alarm Activation Delay

Uint32 Second

n/a

RW

0 - 150

44508

Low Oil Press. Alarm Enable

Uint32 n/a

n/a

RW

0 = Disable

1 = Enable

44510

Low Oil Press. Alarm Threshold

Uint32 PSI

Deci

RW

29 - 1500

44512

Metric Low Oil Press. Alarm Threshold

Uint32 kPa

Deci

RW

200 - 10345

44514

Low Oil Press. Alarm Arming Delay

Uint32 Second

n/a

RW

5 - 60

44516

Overspeed Alarm Enable

Uint32 n/a

n/a

RW

0 = Disable
1 = Enable

44518

Overspeed Alarm Threshold

Uint32 Percent

n/a

RW

105 - 140

44520

Overspeed Alarm Activation Delay

Uint32 Millisecond Milli

RW

0 - 500

44522

Low Fuel Level Alarm Enable

Uint32 n/a

n/a

RW

0 = Disable

1 = Enable

44524

Low Fuel Level Alarm Threshold

Uint32 Percent

n/a

RW

0 - 100

44526

Low Fuel Level Alarm Activation Delay

Int32

Second

n/a

RW

0 - 30

44528

High Coolant Temp Pre-Alarm Enable

Uint32 n/a

n/a

RW

0 = Disable

1 = Enable

44530

High Coolant Temp Pre-Alarm Threshold

Uint32 Deg F

n/a

RW

100 - 280

44532

Metric High Coolant Temp Pre-Alarm Threshold

Int32

Deg C

n/a

RW

38 - 138

44534

Low Coolant Temp Pre-Alarm Enable

Uint32 n/a

n/a

RW

0 = Disable
1 = Enable

44536

Low Coolant Temp Pre-Alarm Threshold

Uint32 Deg F

n/a

RW

35 - 151

44538

Metric Low Coolant Temp Pre-Alarm Threshold

Int32

Deg C

n/a

RW

2 - 66