Legacy Register Table

DGC-2020HD Modbus

™ Protocol

Register

Description

Type

Units

Scaling

Factor

R/W

Range

46556

AEM Input 6 Threshold 2 Activation Delay

Int32

Second

n/a

RW 0 – 300

46558

AEM Input 6 Over 1 Threshold

Int32

Centi Unit

Centi

RW (-100000000) – 99999900

46560

AEM Input 6 Over 2 Threshold

Int32

Centi Unit

Centi

RW (-100000000) – 99999900

46562

AEM Input 6 Under 1 Threshold

Int32

Centi Unit

Centi

RW (-100000000) – 99999900

46564

AEM Input 6 Under 2 Threshold

Int32

Centi Unit

Centi

RW (-100000000) – 99999900

46566

AEM Input 6 Over 1 Alarm Type

Int32

n/a

n/a

RW 0 = Status Only

1 = Pre-Alarm

2 = Alarm

46568

AEM Input 6 Over 2 Alarm Type

Int32

n/a

n/a

RW 0 = Status Only

1 = Pre-Alarm
2 = Alarm

46570

AEM Input 6 Under 1 Alarm Type

Int32

n/a

n/a

RW 0 = Status Only

1 = Pre-Alarm

2 = Alarm

46572

AEM Input 6 Under 2 Alarm Type

Int32

n/a

n/a

RW 0 = Status Only

1 = Pre-Alarm
2 = Alarm

46574

AEM Input 6 Out of Range Alarm Type

Int32

n/a

n/a

RW 0 = Status Only

1 = Pre-Alarm

2 = Alarm

46576

AEM Input 7 Max Voltage

Int32

DeciVolt

Deci

RW 0 - 100

46578

AEM Input 7 Max Current

Int32

Milliamp x
10

Deci

RW 40 - 200

46580

AEM Input 7 Min Voltage

Int32

DeciVolt

Deci

RW 0 - 100

46582

AEM Input 7 Min Current

Int32

Milliamp x

10

Deci

RW 40 - 200

46584

AEM Input 7 Param Max

Int32

Centi Unit

Centi

RW (-100000000) – 99999900

46586

AEM Input 7 Param Min

Int32

Centi Unit

Centi

RW (-100000000) – 99999900

46588

AEM Input 7 Hysteresis

Int32

Deci
Percent

Deci

RW 0 – 1000

46590

AEM Input 7 Arming Delay

Int32

Second

n/a

RW 0 – 300

46592

AEM Input 7 Threshold 1 Activation Delay

Int32

Second

n/a

RW 0 – 300

46594

AEM Input 7 Threshold 2 Activation Delay

Int32

Second

n/a

RW 0 – 300

46596

AEM Input 7 Over 1 Threshold

Int32

Centi Unit

Centi

RW (-100000000) – 99999900

46598

AEM Input 7 Over 2 Threshold

Int32

Centi Unit

Centi

RW (-100000000) – 99999900

46600

AEM Input 7 Under 1 Threshold

Int32

Centi Unit

Centi

RW (-100000000) – 99999900

46602

AEM Input 7 Under 2 Threshold

Int32

Centi Unit

Centi

RW (-100000000) – 99999900

46604

AEM Input 7 Over 1 Alarm Type

Int32

n/a

n/a

RW 0 = Status Only

1 = Pre-Alarm

2 = Alarm

46606

AEM Input 7 Over 2 Alarm Type

Int32

n/a

n/a

RW 0 = Status Only

1 = Pre-Alarm
2 = Alarm

46608

AEM Input 7 Under 1 Alarm Type

Int32

n/a

n/a

RW 0 = Status Only

1 = Pre-Alarm

2 = Alarm

46610

AEM Input 7 Under 2 Alarm Type

Int32

n/a

n/a

RW 0 = Status Only

1 = Pre-Alarm
2 = Alarm

46612

AEM Input 7 Out of Range Alarm Type

Int32

n/a

n/a

RW 0 = Status Only

1 = Pre-Alarm

2 = Alarm

46614

AEM Input 8 Max Voltage

Int32

DeciVolt

Deci

RW 0 - 100

46616

AEM Input 8 Max Current

Int32

Milliamp x
10

Deci

RW 40 - 200

46618

AEM Input 8 Min Voltage

Int32

DeciVolt

Deci

RW 0 - 100

46620

AEM Input 8 Min Current

Int32

Milliamp x

10

Deci

RW 40 - 200

46622

AEM Input 8 Param Max

Int32

Centi Unit

Centi

RW (-100000000) – 99999900

46624

AEM Input 8 Param Min

Int32

Centi Unit

Centi

RW (-100000000) – 99999900

46626

AEM Input 8 Hysteresis

Int32

Deci
Percent

Deci

RW 0 – 1000

46628

AEM Input 8 Arming Delay

Int32

Second

n/a

RW 0 – 300

46630

AEM Input 8 Threshold 1 Activation Delay

Int32

Second

n/a

RW 0 – 300

46632

AEM Input 8 Threshold 2 Activation Delay

Int32

Second

n/a

RW 0 – 300

46634

AEM Input 8 Over 1 Threshold

Int32

Centi Unit

Centi

RW (-100000000) – 99999900

46636

AEM Input 8 Over 2 Threshold

Int32

Centi Unit

Centi

RW (-100000000) – 99999900

46638

AEM Input 8 Under 1 Threshold

Int32

Centi Unit

Centi

RW (-100000000) – 99999900

46640

AEM Input 8 Under 2 Threshold

Int32

Centi Unit

Centi

RW (-100000000) – 99999900

46642

AEM Input 8 Over 1 Alarm Type

Int32

n/a

n/a

RW 0 = Status Only

1 = Pre-Alarm

2 = Alarm

46644

AEM Input 8 Over 2 Alarm Type

Int32

n/a

n/a

RW 0 = Status Only

1 = Pre-Alarm
2 = Alarm

46646

AEM Input 8 Under 1 Alarm Type

Int32

n/a

n/a

RW 0 = Status Only

1 = Pre-Alarm

2 = Alarm