64

9469300991 Rev A

Default Register Table

DGC-2020HD Modbus

™ Protocol

Name

Description

Group

Register

Type

Bytes R/W

Unit

Range

Unit ID Table

ID Repeat Pre Alarm Enable

GG

6114

Uint32

4

R W n/a

Disabled=0
Enabled=1

Remote Display Panel

Enable Programmable Alarm 1

GG

6116

Uint32

4

R W n/a

Disabled=0
Enabled=1

Remote Display Panel

Enable Programmable Alarm 2

GG

6118

Uint32

4

R W n/a

Disabled=0
Enabled=1

Remote Display Panel

Enable Programmable Pre-Alarm 1

GG

6120

Uint32

4

R W n/a

Disabled=0
Enabled=1

Remote Display Panel

Enable Programmable Pre-Alarm 2

GG

6122

Uint32

4

R W n/a

Disabled=0

Enabled=1

Configuration

Name

Description

Group Register

Type

Bytes R/W

Unit

Range

System Configuration

Nominal Frequency

GG

6500

Uint32

4

R W n/a

50 Hz=50

60 Hz=60

System Configuration

Metric English

GG

6502

Uint32

4

R W n/a

English=0

Metric=1

System Configuration

Metric Units

GG

6504

Uint32

4

R W n/a

bar=0
kPa/MPA=1

System Configuration

Alternate Frequency

GG

6506

Float

4

R W Hertz

10 - 90

System Configuration

Aux CT 1

GG

6508

Uint32

4

R W n/a

CT Not Connected=7

Bus 1 Phase A=0
Bus 1 Phase B=1

Bus 1 Phase C=2
Bus 2 Phase A=3

Bus 2 Phase B=4
Bus 2 Phase C=5

Ground Current=6

System Configuration

Aux CT 2

GG

6510

Uint32

4

R W n/a

CT Not Connected=7

Bus 1 Phase A=0
Bus 1 Phase B=1

Bus 1 Phase C=2

Bus 2 Phase A=3
Bus 2 Phase B=4

Bus 2 Phase C=5
Ground Current=6

System Configuration

Aux CT 3

GG

6512

Uint32

4

R W n/a

CT Not Connected=7
Bus 1 Phase A=0

Bus 1 Phase B=1
Bus 1 Phase C=2

Bus 2 Phase A=3
Bus 2 Phase B=4

Bus 2 Phase C=5

Ground Current=6

System Configuration

Aux CT 4

GG

6514

Uint32

4

R W n/a

CT Not Connected=7
Bus 1 Phase A=0

Bus 1 Phase B=1

Bus 1 Phase C=2
Bus 2 Phase A=3

Bus 2 Phase B=4
Bus 2 Phase C=5

Ground Current=6

System Configuration

Engine Rated RPM

GG

6516

Uint32

4

R W n/a

750 - 3600

System Configuration

RPM Adjustment Bandwidth

GG

6518

Uint32

4

R W n/a

0 - 1000

System Configuration

24V Battery

GG

6520

Uint32

4

R W n/a

12V=0
24V=1

System Configuration

Gen CT Low-Line Scale Factor

GG

6522

Float

4

R W n/a

0.001 - 3

System Configuration

Redundant Ethernet

GG

6524

Uint32

4

R W n/a

No=0

Yes=1

Gen Volt
Configuration

Connection

GG

6526

Int32

4

R W n/a

Delta=7
Wye=8

1 Phase AB=0

1 Phase AC=2
Grounded Delta=9

Gen Volt

Configuration

Ratio Primary

GG

6528

Float

4

R W n/a

1 - 500000

Gen Volt

Configuration

Ratio Secondary

GG

6530

Float

4

R W n/a

1 - 600

Gen Volt

Configuration

Rated Primary LL

GG

6532

Float

4

R W Volt

1 - 500000

Bus 1 Volt Config

Connection

GG

6534

Int32

4

R W n/a

Delta=7

Wye=8
1 Phase AB=0

1 Phase AC=2
Grounded Delta=9

Bus 1 Volt Config

Ratio Primary

GG

6536

Float

4

R W n/a

1 - 500000