Basler Electric DGC-2020HD Modbus Protocol User Manual

Page 255

Advertising
background image

9469300991 Rev A

249

DGC-2020HD Modbus

™ Protocol

Legacy Register Table

Register

Description

Type

Units

Scaling

Factor

R/W

Range

44832-33

Status Metering 1

Int32

n/a

n/a

R

Bit 0 = Idle Request
Bit 1 = Lamp Test

Bit 2 = Alarm Silence
Bit 3 = Reset

Bit 4 = Alternate Frequency Override

Bit 5 = Start Delay Bypass
Bit 6 = Cooldown and Stop Request

from Logic
Bit 7 = Cooldown Request from Logic

Bit 8 = External Start Delay
Bit 9 = Off Mode Cooldown

Bit 10 = PF Mode Active
Bit 11 = Var Mode Active

Bit 12 = Cooldown Timer Active

Bit 13 = Engine Running
Bit 14 = Fuel Leak Detect

Bit 15 = Battery Charger Failure
Bit 16 = Low Coolant Level

Bit 17 = Gen Failed
Bit 18 = Gen Stable

Bit 19 = Gen Dead

Bit 20 = Bus Failed
Bit 21 = Bus Stable

Bit 22 = Bus Dead
Bit 23 = Gen Breaker Closed

Bit 24 = Mains Breaker Closed
Bit 25 = Grounded Delta Override

Bit 26 = Battle Override

Bit 27 = Auto Transfer Switch
Bit 28 = Low Line Override

Bit 29 = Single-Phase AC Override
Bit 30 = Single-Phase Override

Bit 31 = EPS Supplying Load

44834

Hours Until Maintenance

Int32

n/a

n/a

RW 0 - 5000

44836

Cum. Total Engine Run Hrs.

Int32

Hour

n/a

R

0 - 99999

44838

Cum. Total Engine Run Min.

Int32

n/a

n/a

R

0 - 59

44840

Cum. Loaded Engine Run Hrs.

Int32

n/a

n/a

R

0 - 99999

44842

Cum. Loaded Engine Run Min.

Int32

n/a

n/a

R

0 - 59

44844

Cum. Unloaded Engine Run Hrs.

Int32

Hour

n/a

R

0 - 99999

44846

Cum. Unloaded Engine Run Min.

Int32

n/a

n/a

R

0 - 59

44848

Cum. Total kW-Hrs

Uint32 kilowatt-

hour

n/a

R

0 - 999999999

44850

Reserved

44852

Commission Date Month

Uint32 n/a

n/a

RW 1 - 12

44854

Commission Date Day

Uint32 n/a

n/a

RW 1 - 31

44856

Commission Date Year

Uint32 n/a

n/a

RW 0 - 99

44858

Session Total Engine Run Hrs.

Int32

Hour

n/a

R

0 - 99999

44860

Session Total Engine Run Min.

Int32

n/a

n/a

R

0 - 59

44862

Session Loaded Engine Run Hrs.

Int32

Hour

n/a

R

0 - 99999

44864

Session Loaded Engine Run Min.

Int32

n/a

n/a

R

0 - 59

44866

Session Unloaded Engine Run Hrs.

Int32

Hour

n/a

R

0 - 99999

44868

Session Unloaded Engine Run Min.

Int32

n/a

n/a

R

0 - 59

44870

Session kW-Hrs

Int32

kilowatt-

hour

n/a

R

0 - 999999999

44872

Cumulative Number of Engine Starts

Uint32 n/a

n/a

RW 0 - 65535

44874

Session Start Date Month

Uint32 n/a

n/a

RW 1 - 12

44876

Session Start Date Day

Uint32 n/a

n/a

RW 1 - 31

44878

Session Start Date Year

Uint32 n/a

n/a

RW 0 - 99

44880

Generator Status

Uint32 n/a

n/a

R

0 = RESET State
1 = READY State

2 = CRANKING State
3 = RESTING State

4 = RUNNING State
5 = ALARM State

6 = PRESTART State
7 = COOLING State

8 = CONNECTING State

9 = DISCONNECT State
10 = PULSING State

11 = UNLOADING State

44882-932

Reserved

Advertising