Basler Electric DGC-2020HD Modbus Protocol User Manual

Page 256

Advertising
background image

250

9469300991 Rev A

Legacy Register Table

DGC-2020HD Modbus

™ Protocol

Register

Description

Type

Units

Scaling

Factor

R/W

Range

44934-35

Protection Alarm Metering

Int32

n/a

n/a

R

Bit 0 = Not Used
Bit 1 = Not Used

Bit 2 = Not Used
Bit 3 = Not Used

Bit 4 = Not Used

Bit 5 = Not Used
Bit 6 = Not Used

Bit 7 = Not Used
Bit 8 = Not Used

Bit 9 = Not Used
Bit 10 = Not Used

Bit 11 = Not Used
Bit 12 = Not Used

Bit 13 = Not Used

Bit 14 = Not Used
Bit 15 = Not Used

Bit 16 = Not Used
Bit 17 = Not Used

Bit 18 = 81 ROC DF/DT Trip
Bit 19 = 78 Vector Shift Trip

Bit 20 = 51-3 Overcurrent

Bit 21 = 40Q Loss of Excitation
Bit 22 = 32 Reverse Power

Bit 23 = 59-2 Overvoltage
Bit 24 = 27-2 Undervoltage

Bit 25 = 51-2 Overcurrent
Bit 26 = 81 Underfrequency

Bit 27 = 81 Overfrequency

Bit 28 = 59-1 Overvoltage
Bit 29 = 27-1 Undervoltage

Bit 30 = 47 Phase Imbalance
Bit 31 = 51-1 Overcurrent

44936

Cumulative Stats - Total Run Hours

Uint32 Hour

n/a

RW 0 - 5999940

44938

Cumulative Stats - Loaded Run Hours

Uint32 Hour

n/a

RW 0 - 5999940

44940

Cumulative Stats - Unloaded Run Hours

Uint32 Hour

n/a

RW 0 - 5999940

44942

Run Stats - Total Run Hours

Uint32 Hour

n/a

RW 0 - 5999940

44944

Run Stats - Loaded Run Hours

Uint32 Hour

n/a

RW 0 - 5999940

44946

Run Stats - Unloaded Run Hours

Uint32 Hour

n/a

RW 0 - 5999940

44948-49

Control Alarm Bits

Uint32 n/a

n/a

R

Bit 0 = Not Used

Bit 1 = Not Used
Bit 2 = Not Used

Bit 3 = Not Used
Bit 4 = Not Used

Bit 5 = Not Used
Bit 6 = Not Used

Bit 7 = Not Used

Bit 8 = Not Used
Bit 9 = Not Used

Bit 10 = Not Used
Bit 11 = Not Used

Bit 12 = Not Used
Bit 13 = Not Used

Bit 14 = Not Used

Bit 15 = Not Used
Bit 16 = Not Used

Bit 17 = Not Used
Bit 18 = Not Used

Bit 19 = Not Used
Bit 20 = Not Used

Bit 21 = Not Used
Bit 22 = Not Used

Bit 23 = Not Used

Bit 24 = Not Used
Bit 25 = Not Used

Bit 26 = ID Repeat
Bit 27 = ID Missing

Bit 28 = Not Used
Bit 29 = Intergenset Comms Failure

Bit 30 = GOV Output Limit

Bit 31 = AVR Output Limit

44950

Global Alarm

Uint32 n/a

n/a

R

Bit 0 = No system alarms in effect

Bit 1 = System alarm(s) in effect

44952

Global Pre-Alarm

Uint32 n/a

n/a

R

Bit 0 = No system pre-alarms in effect

Bit 1 = System pre-alarm(s) in effect