Basler Electric DGC-2020HD Modbus Protocol User Manual

Page 21

Advertising
background image

9469300991 Rev A

15

DGC-2020HD Modbus

™ Protocol

Default Register Table

Name

Description

Group Register Type Bytes R/W

Unit

Range

Low Coolant Level

Contact Input

GG

0344

Uint32 4

R W n/a

None=0
Input 1=1

Input 2=2

Input 3=3
Input 4=4

Input 5=5
Input 6=6

Input 7=7
Input 8=8

Input 9=9

Input 10=10
Input 11=11

Input 12=12
Input 13=13

Input 14=14
Input 15=15

Input 16=16

Low Coolant Level

Contact Recognition

GG

0346

Uint32 4

R W n/a

Always=0

Engine Running=1

Low Coolant Level

Alarm Configuration

GG

0348

Uint32 4

R W n/a

Status Only=0

Pre-Alarm=1
Alarm=2

Low Coolant Level

Activation Delay

GG

0350

Uint32 4

R W Second

0 - 300

Fuel Leak Detect

Contact Input

GG

0352

Uint32 4

R W n/a

None=0

Input 1=1
Input 2=2

Input 3=3
Input 4=4

Input 5=5
Input 6=6

Input 7=7
Input 8=8

Input 9=9

Input 10=10
Input 11=11

Input 12=12
Input 13=13

Input 14=14
Input 15=15

Input 16=16

Fuel Leak Detect

Contact Recognition

GG

0354

Uint32 4

R W n/a

Always=0

Engine Running=1

Fuel Leak Detect

Alarm Configuration

GG

0356

Uint32 4

R W n/a

Status Only=0

Pre-Alarm=1
Alarm=2

Fuel Leak Detect

Activation Delay

GG

0358

Uint32 4

R W Second

0 - 300

Emergency Stop

Contact Input

GG

0360

Uint32 4

R W n/a

None=0

Input 1=1
Input 2=2

Input 3=3
Input 4=4

Input 5=5
Input 6=6

Input 7=7
Input 8=8

Input 9=9

Input 10=10
Input 11=11

Input 12=12
Input 13=13

Input 14=14
Input 15=15

Input 16=16

Emergency Stop

Contact Recognition

GG

0362

Uint32 4

R W n/a

Always=0

Engine Running=1

Emergency Stop

Alarm Configuration

GG

0364

Uint32 4

R W n/a

Status Only=0

Pre-Alarm=1
Alarm=2

Emergency Stop

Activation Delay

GG

0366

Uint32 4

R W Second

0 - 300

Advertising