Metering – Basler Electric DGC-2020HD Modbus Protocol User Manual

Page 250

Advertising
background image

244

9469300991 Rev A

Legacy Register Table

DGC-2020HD Modbus

™ Protocol

Register

Description

Type

Units

Scaling Factor R/W

Range

44540

High Fuel Level Pre-Alarm Threshold

Int32

Percent

n/a

RW

0 - 150

44542

High Fuel Level Pre-Alarm Enable

Int32

n/a

n/a

RW

0 = Disable

1 = Enable

44544

High Fuel Level Pre-Alarm Activation Delay

Int32

Second

n/a

RW

0 - 30

44546

Low Fuel Level Pre-Alarm Enable

Uint32 n/a

n/a

RW

0 = Disable
1 = Enable

44548

Low Fuel Level Pre-Alarm Threshold

Uint32 Percent

n/a

RW

10 - 100

44550

Low Battery Pre-Alarm Enable

Uint32 n/a

n/a

RW

0 = Disable

1 = Enable

44552

Low Battery Pre-Alarm Threshold

Uint32 DeciVolt

Deci

RW

60 - 280

44554

Low Battery Pre-Alarm Activation Delay

Uint32 Second

n/a

RW

1 - 10

44556

Weak Battery Pre-Alarm Enable

Uint32 n/a

n/a

RW

0 = Disable

1 = Enable

44558

Weak Battery Pre-Alarm Threshold

Uint32 DeciVolt

Deci

RW

40 - 280

44560

Weak Battery Pre-Alarm Activation Delay

Uint32 Second

Deci

RW

0 - 100

44562

Battery Overvoltage Pre-Alarm Enable

Uint32 n/a

n/a

RW

0 = Disable
1 = Enable

44564

Low Oil Press. Pre-Alarm Enable

Uint32 n/a

n/a

RW

0 = Disable
1 = Enable

44566

Low Oil Press. Pre-Alarm Threshold

Uint32 PSI

Deci

RW

29 - 1500

44568

Metric Low Oil Press. Pre-Alarm Threshold

Int32

kPa

Deci

RW

20 - 10345

44570-73

Reserved

Uint32 n/a

n/a

RW

0 = Disable

1 = Enable

44574

ECU Comms Fail Pre-Alarm Enable

Int32

n/a

n/a

RW

0 = Disable

1 = Enable

44576

Active DTC Pre-Alarm Enable

Int32

n/a

n/a

RW

0 = Disable

1 = Enable

44578

Maintenance Interval Pre-Alarm Enable

Uint32 n/a

n/a

RW

0 = Disable

1 = Enable

44580

Maintenance Interval Pre-Alarm Threshold

Uint32 Hour

n/a

RW

0 - 5000

44582

Speed Sender Fail Activation Delay

Int32

Second

n/a

RW

0 - 300

44584

ECU Low Coolant Level Alarm Enable

Uint32 n/a

n/a

RW

0 = Disable

1 = Enable

44586

ECU Low Coolant Level Alarm Threshold

Uint32 Percent

n/a

RW

1 - 99

44588

ECU Low Coolant Level Pre-Alarm Enable

Uint32 n/a

n/a

RW

0 = Disable
1 = Enable

44590

ECU Low Coolant Level Pre-Alarm Threshold

Uint32 Percent

n/a

RW

1 - 99

44592

Battery Overvoltage Alarm Threshold

Int32

DeciVolt

Deci

RW

120 - 320

44594-627 Reserved

44628

Intergenset Comm Failure Pre-alarm Enable

Int32

n/a

n/a

RW

0 = Disable
1 = Enable

44630

AVR Bias Output Limit Pre-alarm Activation Delay

Int32

Second

n/a

RW

1 - 15

44632

AVR Bias Output Limit Pre-alarm Enable

Int32

n/a

n/a

RW

0 = Disable

1 = Enable

44634

GOV Bias Output Limit Pre-alarm Activation Delay

Int32

Second

n/a

RW

1 - 15

44636

GOV Bias Output Limit Pre-alarm Enable

Int32

n/a

n/a

RW

0 = Disable

1 = Enable

44638

ID Missing Pre-alarm Enable

Int32

n/a

n/a

RW

0 = Disable

1 = Enable

44640

ID Repeat Pre-alarm Enable

Int32

n/a

n/a

RW

0 = Disable

1 = Enable

44642

CEM Comm Failure Pre-alarm Enable

Int32

n/a

n/a

RW

0 = Disable

1 = Enable

44644

AEM Comm Failure Pre-alarm Enable

Int32

n/a

n/a

RW

0 = Disable

1 = Enable

44646

Reserved

44648

Low Oil Pressure Alarm (metric pressure units is Bar)

Int32

Bar

Deci

RW

2 - 103

44650

Low Oil Pressure Pre-Alarm (metric pressure units is Bar)

Int32

Bar

Deci

RW

2 - 103

44652

Sync Fail Pre-alarm Enable

Int32

n/a

n/a

RW

0 = Disable

1 = Enable

44654

Breaker Close Fail Pre-Alarm Enable

Int32

n/a

n/a

RW

0 = Disable

1 = Enable

44656

Breaker Open Fail Pre-Alarm Enable

Int32

n/a

n/a

RW

0 = Disable

1 = Enable

44658

Breaker Close Fail Pre-Alarm Monitor

Int32

n/a

n/a

RW

0 = Transitions Only

1 = Always

44660

Breaker Open Fail Pre-Alarm Monitor

Int32

n/a

n/a

RW

0 = Transitions Only

1 = Always

44662

Reverse Rotation Pre-Alarm Enable

Uint32 n/a

n/a

RW

0 = Disable

1 = Enable

Metering

Register

Description

Type

Units

Scaling

Factor

R/W

Range

44750

Gen VAB Metering

Int32

Volt

n/a

R

(-2147483648) - 2147483647

44752

Gen VBC Metering

Int32

Volt

n/a

R

(-2147483648) - 2147483647

Advertising