Pulse outputs, Control settings – Basler Electric DGC-2020HD Modbus Protocol User Manual

Page 68

Advertising
background image

62

9469300991 Rev A

Default Register Table

DGC-2020HD Modbus

™ Protocol

Name

Description

Group Register Type Bytes R/W

Unit

Range

Fuel Level Sender Fail

Alarm Configuration

GG

4109

Uint32 4

R W n/a

Status Only=0
Pre-Alarm=1

Alarm=2

Fuel Level Sender Fail

Activation Delay

GG

4111

Uint32 4

R W Second 0 - 300

Voltage Sensing Sender
Fail

Alarm Configuration

GG

4113

Uint32 4

R W n/a

Status Only=0
Pre-Alarm=1

Alarm=2

Voltage Sensing Sender

Fail

Activation Delay

GG

4115

Uint32 4

R W Second 0 - 300

Single Ph Override

Single-Phase Sense

GG

4117

Uint32 4

R W n/a

AB=0

AC=1

AVR Output

Out-of-Range Activation Delay

GG

4119

Float

4

R W Second 0 - 300

AVR Output

Alarm Configuration

GG

4121

Uint32 4

R W n/a

Status Only=0

Pre-Alarm=1
Alarm=2

GOV Output

Out-of-Range Activation Delay

GG

4123

Float

4

R W Second 0 - 300

GOV Output

Alarm Configuration

GG

4125

Uint32 4

R W n/a

Status Only=0

Pre-Alarm=1
Alarm=2

LS Output

Out of Range Activation Delay

GG

4127

Float

4

R W Second 0 - 300

LS Output

Alarm Configuration

GG

4129

Uint32 4

R W n/a

Status Only=0
Pre-Alarm=1

Alarm=2

Pulse Outputs

Name

Description

Group

Register

Type

Bytes

R/W

Unit

Range

AVR Pulse Output

Mode

GG

5000

Uint32

4

R W

n/a

Continuous=0

Proportional=1

AVR Pulse Output

Correction Pulse Width

GG

5002

Float

4

R W

Second

0 - 99.9

AVR Pulse Output

Correction Pulse Interval

GG

5004

Float

4

R W

Second

0 - 99.9

GOV Pulse Output

Mode

GG

5006

Uint32

4

R W

n/a

Continuous=0

Proportional=1

GOV Pulse Output

Correction Pulse Width

GG

5008

Float

4

R W

Second

0 - 99.9

GOV Pulse Output

Correction Pulse Interval

GG

5010

Float

4

R W

Second

0 - 99.9

Control Settings

Name

Description

Group Register Type Bytes R/W Unit

Range

Virtual Switch

Virtual Switch 1 State

GG

5500

Uint32 4

R W n/a

Open=0
Closed=1

Virtual Switch

Virtual Switch 2 State

GG

5502

Uint32 4

R W n/a

Open=0
Closed=1

Virtual Switch

Virtual Switch 3 State

GG

5504

Uint32 4

R W n/a

Open=0

Closed=1

Virtual Switch

Virtual Switch 4 State

GG

5506

Uint32 4

R W n/a

Open=0

Closed=1

Virtual Switch

Virtual Switch 5 State

GG

5508

Uint32 4

R W n/a

Open=0

Closed=1

Virtual Switch

Virtual Switch 6 State

GG

5510

Uint32 4

R W n/a

Open=0

Closed=1

Coms Control Group

Emergency Stop: Writing a 1 will toggle

emergency stop from off to on. Writing a 1
again will toggle emergency stop from on to

off. When read, Off state =0 and On state =1.

GG

5512

Uint32 4

R W n/a

Toggle On/Off=1

Coms Control Group

Remote Start

GG

5514

Uint32 4

R W n/a

Trigger=1

Coms Control Group

Remote Stop

GG

5516

Uint32 4

R W n/a

Trigger=1

Coms Control Group

Run Mode

GG

5518

Uint32 4

R W n/a

Trigger=1

Coms Control Group

Off Mode

GG

5520

Uint32 4

R W n/a

Trigger=1

Coms Control Group

Auto Mode

GG

5522

Uint32 4

R W n/a

Trigger=1

Coms Control Group

Gen Breaker Open Request

GG

5524

Uint32 4

R W n/a

Trigger=1

Coms Control Group

Gen Breaker Close Request

GG

5526

Uint32 4

R W n/a

Trigger=1

Coms Control Group

Mains Breaker Open Request

GG

5528

Uint32 4

R W n/a

Trigger=1

Coms Control Group

Mains Breaker Close Request

GG

5530

Uint32 4

R W n/a

Trigger=1

Coms Control Group

Emergency Stop

GG

5532

Uint32 4

R W n/a

Trigger=1

Coms Control Group

Run Request

GG

5534

Uint32 4

R W n/a

Trigger=1

Coms Control Group

Coms Alarm Reset

GG

5536

Uint32 4

R W n/a

Trigger=1

Coms Control Group

Reset Generator Maximum ROCOF

GG

5538

Uint32 4

R W n/a

Trigger=1

Coms Control Group

Reset Bus 1 Maximum ROCOF

GG

5540

Uint32 4

R W n/a

Trigger=1

Coms Control Group

Reset Bus 2 Maximum ROCOF

GG

5542

Uint32 4

R W n/a

Trigger=1

Coms Control Group

Reset Generator Maximum Vector Shift

GG

5544

Uint32 4

R W n/a

Trigger=1

Coms Control Group

Reset Bus 1 Maximum Vector Shift

GG

5546

Uint32 4

R W n/a

Trigger=1

Coms Control Group

Reset Bus 2 Maximum Vector Shift

GG

5548

Uint32 4

R W n/a

Trigger=1

Advertising