Basler Electric DGC-2020HD Modbus Protocol User Manual

Page 200

Advertising
background image

194

9469300991 Rev A

Default Register Table

DGC-2020HD Modbus

™ Protocol

Name

Description

Group Register Type Bytes R/W

Unit

Range

51-5

Mode

SG1 3P 24140

Uint32 4

R W n/a

Disabled=0
IA=1

IB=2

IC=3
Imax=4

3I0=5
I2=6

IG=7
I1=8

51-5

Source

SG1 3P 24142

Uint32 4

R W n/a

Gen=0
Bus 1=1

Bus 2=2

51-5

Pickup

SG1 3P 24144

Float

4

R W Amp

0.9 - 7.75

51-5

Curve Index

SG1 3P 24146

Uint32 4

R W n/a

S1=0
S2=1

L1=2
L2=3

D=4
M=5

I1=6
I2=7

V1=8

V2=9
E1=10

E2=11
A=12

B=13
C=14

G=15

F=16
46=17

P=18

51-5

Direction

SG1 3P 24148

Uint32 4

R W n/a

Forward=0

Reverse=1
Non-Directional=2

51-5

Use Instantaneous Reset

SG1 3P 24150

Uint32 4

R W n/a

Integrating=0

Instantaneous=1

51-5

Constant TD

SG1 3P 24152

Float

4

R W n/a

0 - 9.9

51-5

Constant A

SG1 3P 24154

Float

4

R W n/a

0 - 600

51-5

Constant B

SG1 3P 24156

Float

4

R W n/a

0 - 25

51-5

Constant C

SG1 3P 24158

Float

4

R W n/a

0 - 1

51-5

Constant N

SG1 3P 24160

Float

4

R W n/a

0.5 - 2.5

51-5

Constant R

SG1 3P 24162

Float

4

R W n/a

0 - 30

51-5

Voltage Restraint Setpoint

SG1 3P 24164

Float

4

R W Volt

30 - 250

51-5

Voltage Restraint Mode

SG1 3P 24166

Uint32 4

R W n/a

Disabled=0
Control=1

Restraint=2

51-5

Alarm Configuration

SG1 3P 24168

Uint32 4

R W n/a

Status Only=0

Pre-Alarm=1
Alarm=2

51-5

Low-Line Scale

SG1 3P 24170

Float

4

R W n/a

0.001 - 3

51-5

Voltage Restraint Source

SG1 3P 24172

Uint32 4

R W n/a

Gen=0
Bus 1=1

Bus 2=2

51-5

Constant Q

SG1 3P 24174

Float

4

R W n/a

0.1 - 10

51-5

Mode

SG2 1P 24176

Uint32 4

R W n/a

Disabled=0
IA=1

IB=2
IC=3

Imax=4
3I0=5

I2=6

IG=7
I1=8

51-5

Source

SG2 1P 24178

Uint32 4

R W n/a

Gen=0

Bus 1=1

Bus 2=2

51-5

Pickup

SG2 1P 24180

Float

4

R W Amp

0.9 - 7.75